1 .. 239 240 241 242 243 244 245 246 247 248 249 .. 908
1 - 239
2. EXTERNAL DIMENSIONS
YKB/YLM 2nd
BC
MEE15K022
(Note 2.)
X
Connection pipe of
indoor unit(Gas)
Connection pipe of
indoor unit(Liquid)
Band(Accessory)
250
(700)
200
Access
door
450
(200)
Indoor unit model (Note 5.)
P50 or less:
Ø
6.35<Brazed>
P50 over
:
Ø
9.52<Brazed>
Indoor unit model (Note 5.)
P50 or less:
Ø
12.7<Brazed>
P50 over
:
Ø
15.88<Brazed>
Connection pipe of MAIN BC CONTROLLER   
(Low pressure)
Connection pipe of MAIN BC CONTROLLER                
(High pressure)
30
14
12
130
130
130
23
Connection pipe of MAIN BC CONTROLLER(Liquid)      
Ø
31
(Lifting bolt pitch)
Detail of
Y
 section
Detail of X section
Y
298
362
Control box
70
1098
60X15=900
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
60
46
1
152
58
27
128
255
284
103
169
248
45
181
90
200
76
60
60X15=900
(Lifting bolt pitch)
Service
 space
T
otal capacity of indoor units at SUB BC CONTROLLER
P200 or less:
Ø
19.05<Brazed>(use attachment pipe)
P300 or less:
Ø
22.2 <Brazed>
P300 over
:
Ø
28.58<Brazed>(use attachment pipe)
T
otal capacity of indoor units at SUB BC CONTROLLER
P300 or less:
Ø
9.52 <Brazed>
P300 over
:
Ø
12.7 <Brazed>(use attachment pipe)
T
otal capacity of indoor units at SUB BC CONTROLLER
P200 or less:
Ø
15.88<Brazed>(use attachment pipe)
P200 over
:
Ø
19.05<Brazed>
Note1.Suspension bolt(
Ø
10),washer(M10),and nut(M10)
      prepare in the field.
    2.T
ake notice of service space as follows.
      (Please give attention not to occupy service
      space by letting ducts and pipes through.)  
    3.Can't use singleness.(MAIN BC CONTROLLER is necessary
.)
    4.Install this product in a location where noise (refrigerant noise)
      emitted by the unit will not disturb the neighbors.
    (For use in quiet enviroments with low background noise,position
     the BC CONTROLLER at least 5m away from any indoor units.)
    5.Refer to the Installation Manual for refrigerant piping diameter size
      when connecting plural indoor units with 1 branch.
<Accessories>
Refrigerant<Low pressure> conn. pipe
··············
4pcs.
Refrigerant<High pressure> conn. pipe
·············
2pcs.
Refrigerant<Liquid> conn. pipe
························
2pcs.
Drain hose I.D.32 (1-1/4”)
·······························
1pc.
Hose band
···················································
1pc.
T
ie band
······················································
1pc.
Drain pipe O.D.32 (1-1/4”)
Drain hose I.D.32 (1-1/4”)
Z
Detail of Z section
Cutting point
Cutting point
(Indoor unit Model:P50 or less)
(Indoor unit Model:P50 over)
CMB-P1016V
-HB1
Unit : mm