1 - 234
BC
1. SPECIFICATIONS
YKB/YLM 2nd
MEE15K022
Model name
CMB-P1016V-HB1
Number of branch
16
Power source
1-phase 220/230/240V
50Hz
60Hz
Power input
Cooling
kW
0.237/0.269/0.301
0.192/0.216/0.237
(220/230/240)
Heating
0.119/0.135/0.151
0.096/0.108/0.120
Current
Cooling
A
1.08/1.17/1.26
0.88/0.94/0.99
(220/230/240)
Heating
0.55/0.59/0.63
0.44/0.47/0.50
External finish
Galvanized steel plate
(Lower part drain pan painting N1.5)
Connectable BC controller
Main BC
CMB-P108/1010/1013/1016V-GA1,CMB-P1016V-HA1
Sub BC
CMB-P104/108V-GB1, CMB-P1016V-HB1
Indoor unit capacity
Model P80 or smaller
connectable to 1 branch
(Use optional joint pipe combining 2 branches when the total unit capacity exceeds 81.)
External dimension H x W x D
mm (in.
)
284 x 1,098 x 432 (11-3/16 x 43-1/4 x 17-1/32)
Refrigerant
Connectable outdoor unit
To outdoor unit
piping
capacity
High press. pipe
Low press.
pipe
diameter
mm (in.
) O.
D.
-
-
To indoor unit
Liquid pipe
Gas pipe
mm (in.
) O.
D.
Indoor unit Model 50 or smaller
6.35 (1/4) Brazed
Indoor unit Model 50 or smaller
12.7 (1/2) Brazed
bigger than 50
9.52 (3/8) Brazed
bigger than 50
15.88 (5/8) Brazed
(12.7 (1/2) with optional joint pipe used.)
(19.05 (3/4), 22.2 (7/8) with optional joint pipe used.)
Total indoor unit capacity
To other BC controller
connected to this Sub BC
High press. pipe
Low press.
pipe
controller
Liquid pipe
to P200
15.88 (5/8) Brazed
19.05 (3/4) Brazed
mm (in.
) O.
D.
9.52 (3/8) Brazed
P201 to P300
19.05 (3/4) Brazed
22.2 (7/8) Brazed
mm (in.
) O.
D.
9.52 (3/8) Brazed
P301 to P350
19.05 (3/4) Brazed
28.58 (1-1/8) Brazed
mm (in.
) O.
D.
12.7 (1/2) Brazed
P351 to P400
22.2 (7/8) Brazed
28.58 (1-1/8) Brazed
mm (in.
) O.
D.
12.7 (1/2) Brazed
P401 to P450
22.2 (7/8) Brazed
28.58 (1-1/8) Brazed
mm (in.
) O.
D.
15.88 (5/8) Brazed
Field drain pipe size
mm (in.
) O.
D.
32 (1-1/4)
Net weight
kg (lbs)
55 (122)
Accessories
Drain Connection pipe (with flexible hose and insulation)
Reducer
Remark
Note:
1. Installation/foundation work, electrical connection work, insulation work, power source switch, and other items shall be referred to the Installation Manual.
2. The equipment is for R410A refrigerant.
3. For sub BC controller CMB-P1016V-HB1 the connectable indoor unit capacities may sum to equal that of a P350 unit or less. However, if two sub controllers are used
the TOTAL sum of connectable units connected to BOTH sub controllers must also not exceed that a P450 unit.
4. To use the Sub BC controller, the Main BC controller is necessary to be connected with.
5. Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors.
(For use in quiet environments with low background noise, position the BC CONTROLLER at least 5m away from any indoor units.)
6. Indoor units P100, P125, P140 can be connected to 1 branch.
(In this case, cooling capacity decrease a little.
)
7. Refrigerant piping diameter for connection of plural indoor units with 1 branch shall be referred to the Installation Manual.