1 - 237
2. EXTERNAL DIMENSIONS
YKB/YLM 2nd
BC
MEE15K022
Detail of Z section
Cutting point
Cutting point
(Indoor unit Model:P50 or less)
(Indoor unit Model:P50 over)
Ø
31
(Note 2,3.)
200
200
(700)
250
Drain hose I.D.32 (1-1/4”)
Band(Accessory)
Access
door
450
(200)
Connection pipe of
indoor unit(Gas)
Indoor unit model (Note 6.)
P50 or less:
Ø
12.7<Brazed>
P50 over
:
Ø
15.88<Brazed>
Indoor unit model (Note 6.)
P50 or less:
Ø
6.35<Brazed>
P50 over
:
Ø
9.52<Brazed>
Connection pipe of
indoor unit(Liquid)
T
otal capacity of indoor unit
at SUB BC CONTROLLER
P200 or less:
Ø
19.05<Brazed>
(use attachment pipe of
SUB BC CONTROLLER)
P300 or less:
Ø
22.2<Brazed>
P300 over:
Ø
28.58<Brazed>
(use attachment pipe of
SUB BC CONTROLLER)
Connection pipe of
SUB BC CONTROLLER
(Low pressure)
T
otal capacity of indoor unit
at SUB BC CONTROLLER
P300 or less :
Ø
9.52<Brazed>
P400 or less :
Ø
12.7<Brazed>
(use attachment pipe of
SUB BC CONTROLLER)
P400 over:
Ø
15.88<Brazed>
(use attachment pipe of
JOINT<option>)
Connection pipe of
SUB BC CONTROLLER
(Liquid)
T
otal capacity of indoor unit
at SUB BC CONTROLLER
P200 or less:
Ø
15.88<Brazed>
(use attachment pipe of
SUB BC CONTROLLER)
P350 or less:
Ø
19.05<Brazed>
P350 over:
Ø
22.2<Brazed>
(use attachment pipe of
JOINT<option>)
Connection pipe of
SUB BC CONTROLLER
(High pressure)
Drain pipe O.D.32 (1-1/4”)
30
12
14
60X15=900
60
76
130
130
130
23
(Lifting bolt pitch)
Connection pipe of outdoor unit(Low pressure)
Connection pipe of outdoor unit
(High pressure)
Detail of
Y
section
Detail of X section
Control box
1
164
111
0
388
450
70
46
60X15=900
60
90
90
1
2
3
4
5
6
7
8
9
1
0
1
1
1
2
1
3
1
4
1
5
1
6
74
103
210
268
66
128
103
268
333
27
74
128
260
289
Y
X
200
Ø
28.58 <Brazed>
(Lifting bolt pitch)
Service
space
P700 to P800 :
Ø
34.93<Brazed>(use attachment pipe)
P850, P900 :
Ø
41.28<Brazed>
Note1.Suspension bolt(
Ø
10),washer(M10),and nut(M10)
prepare in the field.
2.T
ake notice of service space as follows.
(Please give attention not to occupy service
space by letting ducts and pipes through.)
3.Please take service space for connection pipe of SUB BC CONTROLLER.
4.When using an outdoor unit-28HP(P700) or more,use this product.
5.Install this product in a location where noise (refrigerant noise)
emitted by the unit will not disturb the neighbors.
(For use in quiet enviroments with low background noise,position
the BC CONTROLLER at least 5m away from any indoor units.)
6.Refer to the Installation Manual for refrigerant piping diameter size
when connecting plural indoor units with 1 branch.
<Accessories>
Refrigerant<Low pressure> conn. pipe
·····
1pc.
Drain hose I.D.32 (1-1/4”)
······················
1pc.
Hose band
··········································
1pc.
T
ie band
·············································
1pc.
Z
CMB-P1016V
-HA1
Unit : mm