1 - 10
PE
F
Y
MEE15K022
1. SPECIFICATIONS
YKB/YLM 2nd
Model
PEFY-P200VMHS-E
PEFY-P250VMHS-E
Power source
1-phase 220-230-240V
50/60Hz
1-phase 220-230-240V
50/60Hz
Cooling capacity
*1
kW
22.4
28.0
(Nominal)
*1
kcal / h
19,300
24,100
*1
BTU / h
76,400
95,500
*2
Power input
kW
0.63
0.82
*2
Current input
A
3.47 - 3.32 - 3.18
(220-230-240V)
4.72 - 4.43 - 4.14
(220-230-240V)
Heating capacity
*3
kW
25.0
31.5
(Nominal)
*3
kcal / h
21,500
27,100
*3
BTU / h
85,300
107,500
*2
Power input
kW
0.63
0.82
*2
Current input
A
3.47 - 3.32 - 3.18
(220-230-240V)
4.72 - 4.43 - 4.14
(220-230-240V)
External finish
Galvanized steel plate
Galvanized steel plate
External dimension HxWxD
mm
470 x 1,250 x 1,120
470 x 1,250 x 1,120
inch
18-1/2 x 49-1/4 x 44-1/8
18-1/2 x 49-1/4 x 44-1/8
Net weight
kg(lbs)
97(214)
100(221)
Heat exchanger
Cross fin (Aluminum fin and
copper tube)
Cross fin (Aluminum fin and
copper tube)
FAN
Type x Quantity
Sirocco fan x 2
Sirocco fan x 2
*4
External static press.
Pa
<50> - <100> - 150 -
<200> - <250>
<50> - <100> - 150 -
<200> - <250>
mmH
2
O
<5.1> - <10.2> - 15.3 - <20.4>
- <25.5>
<5.1> - <10.2> - 15.3 - <20.4>
- <25.5>
Motor Type
DC motor
DC motor
Motor output
kW
0.870
0.870
Driving mechanism
Inverter-control
Inverter-control
Air flow rate
(Low-Mid-High)
(Low-Mid-High)
m
3
/ min
50.0 - 61.0 - 72.0
58.0 - 71.0 - 84.0
L/s
833 - 1,017 - 1,200
967 - 1,183 - 1,400
cfm
1,766 - 2,154 - 2,542
2,048 - 2,507 - 2,966
Sound pressure level (measured in anechoic room)
(Low-Mid-High)
(Low-Mid-High)
*2
dB <A>
36-39-43
39-42-46
Insulation material
EPS, Polyethylene foam, Ure-
thane foam
EPS, Polyethylene foam, Ure-
thane foam
Air filter
Option: Synthetic fiber unwo-
ven cloth filter (long life filter)
and filter box are recommend-
ed.
Option: Synthetic fiber unwo-
ven cloth filter (long life filter)
and filter box are recommend-
ed.
Protection device
Fuse
Fuse
Refrigerant control device
LEV
LEV
Connectable outdoor unit
R410A CITY MULTI
R410A CITY MULTI
Diameter of refrigerant
Liquid (R410A)
mm(inch)
9.52(3/8")Brazed
9.52(3/8")Brazed
pipe
Gas (R410A)
mm(inch)
19.05(3/4")Brazed
22.22(7/8")Brazed
Field drain pipe size
mm(inch)
O.
D.
32(1-1/4")
O.D.32(1-1/4")
Drawing
External
KD94G757
KD94G757
Wiring
KD94G911
KD94G911
Refrigerant cycle
-
-
Standard attachment
Document
Installation Manual, Instruc-
tion Book
Installation Manual, Instruc-
tion Book
Accessory
Insulation pipe for refrigerant
pipe, Washer, Drain hose, Tie
band
Insulation pipe for refrigerant
pipe, Washer, Drain hose, Tie
band
Optional parts
Drain pump kit
PAC-KE05DM-F
PAC-KE05DM-F
Long life filter
PAC-KE85LAF
PAC-KE85LAF
Filter box
PAC-KE250TB-F
PAC-KE250TB-F
Remark
* Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be
referred to the Installation Manual.
* Due to continuing improvement, above specifications may be subject to change without notice.
Notes:
Unit converter
1.Nominal cooling conditions (subject to JIS B8615-2)
Indoor: 27°CDB/19°CWB (81°FDB/66°FWB), Outdoor: 35°CDB (95°FDB)
Pipe length: 7.5m (24-9/16"ft.
), Level difference: 0m (0ft.)
kcal/h
BTU/h
cfm
lbs
=kW x 860
=kW x 3,412
=m
3
/min x 35.31
=kg/0.4536
2.The values are measured at the factory setting of external static pressure.
3.Nominal heating conditions (subject to JIS B8615-2)
Indoor: 20°CDB (68°FDB), Outdoor: 7°CDB/6°CWB (45°FDB/43°FWB)
Pipe length: 7.5m (24-9/16"ft.
) Level, difference: 0m(0ft.
)
*Above specification data is
subject to rounding variation.
4.The factory setting of external static pressure is shown without < >.
Refer to "Fan characteristics curves", according to the external static pressure,
in DATA BOOK for the usable range of air flow rate.