1 .. 7 8 9 10 11 12 13 14 15 16 17 .. 908
1 - 7
PEFY
MEE15K022
1. SPECIFICATIONS
YKB/YLM 2nd
Model
Power source
Cooling capacity
(Nominal)
Heating capacity
(Nominal )
 
External finish
External dimension H x W x D
Net weight
Heat exchanger
FAN
Sound pressure level (Low-Mid-High)
 (measured in anechoic room)
Insulation material
Air filter
Protection device
Refrigerant control device
Connectable outdoor unit
Diameter of
refrigerant pipe
Field drain pipe size
Drawing
Standard
attachment
Remark
Power input
Current input
Power input
Current input
Type x Quantity
External
static press.
Motor type
Motor output
Driving mechanism
Airflow rate
(Low-Mid-High)
Liquid
Gas
External
Wiring
Refrigerant cycle
Document
Accessory
Optional parts
Installation
kW
kcal / h
BTU / h
kcal / h
kW
A
kW
kcal / h
BTU / h
kW
A
mm
in.
kg (lbs)
Pa
mmH
2
O
Pa
mmH
2
O
kW
m
3
 / min
L / s
cfm
dB <A>
dB <A>
 
mm (in.)
mm (in.)
 
mm (in.)
*1
*1
*1
*2
*3
*3
*3
(R410A)
(R410A)
*5
*4
*4
*4
*4
*4
(220V)
(230, 240V)
*1 Nominal cooling conditions
*4 The values are measured at the factory setting of external static pressure.
Note :
Indoor :
Outdoor :
Pipe length :
Level difference :
27°CDB/19°CWB (81°FDB/66°FWB)
35°CDB (95°FDB)
7.5 m (24-9/16 ft)
0 m (0 ft)
*2 Nominal cooling conditions
27°CDB/19.5°CWB (81°FDB/67°FWB)
35°CDB (95°FDB)
5 m (16-3/8 ft)
0 m (0 ft)
*3 Nominal heating conditions
Unit converter
20°CDB (68°FDB)
7°CDB/6°CWB (45°FDB/43°FWB)
7.5 m (24-9/16 ft)
0 m (0 ft)
* Due to continuing improvement, above specification may be subject to change without notice.
* Nominal conditions *1, *3 are subject to JIS B8615-2.
kcal/h
= kW x 860
BTU/h
= kW x 3,412
cfm
=
m
3
/min x 35.31
lbs
= kg / 0.4536
*Above specification data is
subject to rounding variation.
Cross fin (Aluminum fin and copper tube)
1-phase induction motor
Direct-driven by motor
Polystyrene foam, Polyethylene foam, Urethane foam
Optional long life filter (Synthetic fiber unwoven cloth filter) and filter box are recommended.
Fuse
LEV
 R410A CITY MULTI
IU-W27-5924
IU-W65-3956
-
 Installation Manual, Instruction Book
Drain hose I.D. 32mm (1-1/4) (flexible joint)
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to
the Installation Manual.
PEFY-P40VMH-E
1-phase 220-240V 50Hz/60Hz
4.5
3,900
15,400
4,000
0.19 / 0.23
0.88 / 1.06
5.0
4,300
17,100
0.19 / 0.23
0.88 / 1.06
380 x 750 x 900
15 x 29-9/16 x 35-7/16
41 (91)
Sirocco fan x 1
0.080
10.0 - 14.0
167 - 233
353 - 494
ø6.35 (ø1/4) Flare
ø12.7 (ø1/2) Flare
(220V)
(230, 240V)
27 - 34
31 - 37
PEFY-P50VMH-E
5.6
4,800
19,100
5,000
0.19 / 0.23
0.88 / 1.06
6.3
5,400
21,500
0.19 / 0.23
0.88 / 1.06
380 x 750 x 900
15 x 29-9/16 x 35-7/16
41 (91)
Sirocco fan x 1
0.080
10.0 - 14.0
167 - 233
353 - 494
ø6.35 (ø1/4) Flare
ø12.7 (ø1/2) Flare
(220V)
(230, 240V)
27 - 34
31 - 37
PEFY-P63VMH-E
7.1
6,100
24,200
6,300
0.24 / 0.30
1.12 / 1.38
8.0
6,900
27,300
0.24 / 0.30
1.12 / 1.38
380 x 750 x 900
15 x 29-9/16 x 35-7/16
41 (91)
Sirocco fan x 1
0.120
13.5 - 19.0
225 - 317
477 - 671
ø9.52 (ø3/8) Flare
ø15.88 (ø5/8) Flare
32 - 38
36 - 41
PEFY-P71VMH-E
8.0
6,900
27,300
7,100
0.26 / 0.33
1.20 / 1.51
9.0
7,700
30,700
0.26 / 0.33
1.20 / 1.51
380 x 1,000 x 900
15 x 39-3/8 x 35-7/16
50 (111)
Sirocco fan x 1
0.140
15.5 - 22.0
258 - 367
547 - 777
ø9.52 (ø3/8) Flare
ø15.88 (ø5/8) Flare
(220V)
(230, 240V)
32 - 39
35 - 41
Galvanized
<50> - 100 - <200>
<5.1> - 10.2 - <20.4>
<100> - 150 - <200>
<10.2> - 15.3 - <20.4>
<50> - 100 - <200>
<5.1> - 10.2 - <20.4>
<100> - 150 - <200>
<10.2> - 15.3 - <20.4>
(220V)
(230, 240V)
<50> - 100 - <200>
<5.1> - 10.2 - <20.4>
<100> - 150 - <200>
<10.2> - 15.3 - <20.4>
<50> - 100 - <200>
<5.1> - 10.2 - <20.4>
<100> - 150 - <200>
<10.2> - 15.3 - <20.4>
Long life filter
Filter box
Drain pump
PAC-KE86LAF
PAC-KE63TB-F
PAC-KE04DM-F
PAC-KE86LAF
PAC-KE63TB-F
PAC-KE04DM-F
PAC-KE86LAF
PAC-KE63TB-F
PAC-KE04DM-F
PAC-KE88LAF
PAC-KE80TB-F
PAC-KE04DM-F
O.D. 32mm (1-1/4)
*5 The factory setting of external static pressure is shown without < >.
Refer to "Fan characteristics curves", according to the external static pressure, in DATA BOOK for the usable range of air flow rate.