1. SPECIFICATIONS
YKB/YLM 2nd
Model
Power source
Cooling capacity
(Nominal)
Heating capacity
(Nominal )
 
External finish
External dimension H x W x D
Net weight
Heat exchanger
FAN
Sound pressure level (Low-Mid-High)
 (measured in anechoic room)
Insulation material
Air filter
Protection device
Refrigerant control device
Connectable outdoor unit
Diameter of
refrigerant pipe
Field drain pipe size
Drawing
Standard
attachment
Remark
Power input
Current input
Power input
Current input
Type x Quantity
External
static press.
Motor type
Motor output
Driving mechanism
Airflow rate
(Low-Mid-High)
Liquid
Gas
External
Wiring
Refrigerant cycle
Document
Accessory
Optional parts
Installation
kW
kcal / h
BTU / h
kcal / h
kW
A
kW
kcal / h
BTU / h
kW
A
mm
in.
kg (lbs)
Pa
mmH
2
O
Pa
mmH
2
O
kW
m
3
 / min
L / s
cfm
dB <A>
dB <A>
 
mm (in.)
mm (in.)
 
mm (in.)
*1
*1
*1
*2
*3
*3
*3
(R410A)
(R410A)
*5
*4
*4
*4
*4
*4
(220V)
(230, 240V)
*1 Nominal cooling conditions
*4 The values are measured at the factory setting of external static pressure.
Note :
Indoor :
Outdoor :
Pipe length :
Level difference :
27°CDB/19°CWB (81°FDB/66°FWB)
35°CDB (95°FDB)
7.5 m (24-9/16 ft)
0 m (0 ft)
*2 Nominal cooling conditions
27°CDB/19.5°CWB (81°FDB/67°FWB)
35°CDB (95°FDB)
5 m (16-3/8 ft)
0 m (0 ft)
*3 Nominal heating conditions
Unit converter
20°CDB (68°FDB)
7°CDB/6°CWB (45°FDB/43°FWB)
7.5 m (24-9/16 ft)
0 m (0 ft)
* Due to continuing improvement, above specification may be subject to change without notice.
* Nominal conditions *1, *3 are subject to JIS B8615-2.
kcal/h
= kW x 860
BTU/h
= kW x 3,412
cfm
=
m
3
/min x 35.31
lbs
= kg / 0.4536
*Above specification data is
subject to rounding variation.
Cross fin (Aluminum fin and copper tube)
1-phase induction motor
Direct-driven by motor
Polystyrene foam, Polyethylene foam, Urethane foam
Option : Synthetic fiber unwoven cloth filter (long life)
Fuse
LEV
 R410A CITY MULTI
IU-W27-5924
IU-W65-3956
-
 Installation Manual, Instruction Book
Drain hose I.D. 32mm (1-1/4) (flexible joint)
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to
the Installation Manual.
PEFY-P80VMH-E
1-phase 220-240V 50Hz/60Hz
9.0
7,700
30,700
8,000
0.32 / 0.40
1.47 / 1.83
10.0
8,600
34,100
0.32 / 0.40
1.47 / 1.83
380 x 1,000 x 900
15 x 39-3/8 x 35-7/16
50 (111)
Sirocco fan x 1
0.180
18.0 - 25.0
300 - 417
636 - 883
ø9.52 (ø3/8) Flare
ø15.88 (ø5/8) Flare
(220V)
(230, 240V)
35 - 41
38 - 43
PEFY-P100VMH-E
11.2
9,600
38,200
10,000
0.48 / 0.58
2.34 / 2.66
12.5
10,800
42,700
0.48 / 0.58
2.34 / 2.66
380 x 1,200 x 900
15 x 47-1/4 x 35-7/16
65 (144)
Sirocco fan x 2
0.260
26.5 - 38.0
442 - 633
936 - 1,342
ø9.52 (ø3/8) Flare
ø15.88 (ø5/8) Flare
(220V)
(230, 240V)
34 - 42
38 - 44
PEFY-P125VMH-E
14.0
12,000
47,800
12,500
0.48 / 0.58
2.34 / 2.66
16.0
13,800
54,600
0.48 / 0.58
2.34 / 2.66
380 x 1,200 x 900    
15 x 47-1/4 x 35-7/16     
65 (144)
Sirocco fan x 2
0.260
26.5 - 38.0
442 - 633
936 - 1,342
ø9.52 (ø3/8) Flare
ø15.88 (ø5/8) Flare
34 - 42
38 - 44
PEFY-P140VMH-E
16.0
13,800
54,600
14,000
0.48 / 0.59
2.35 / 2.70
18.0
15,500
61,400
0.48 / 0.59
2.35 / 2.70
380 x 1,200 x 900    
15 x 47-1/4 x 35-7/16     
67 (148)
Sirocco fan x 2
0.260
28.0 - 40.0
467 - 667
989 - 1,413
ø9.52 (ø3/8) Flare
ø15.88 (ø5/8) Flare
(220V)
(230, 240V)
34 - 42
38 - 44
Galvanized
<50> - 100 - <200>
<5.1> - 10.2 - <20.4>
<100> - 150 - <200>
<10.2> - 15.3 - <20.4>
<50> - 100 - <200>
<5.1> - 10.2 - <20.4>
<100> - 150 - <200>
<10.2> - 15.3 - <20.4>
(220V)
(230, 240V)
<50> - 100 - <200>
<5.1> - 10.2 - <20.4>
<100> - 150 - <200>
<10.2> - 15.3 - <20.4>
<50> - 100 - <200>
<5.1> - 10.2 - <20.4>
<100> - 150 - <200>
<10.2> - 15.3 - <20.4>
Long life filter
Filter box
 
Drain pump
PAC-KE88LAF
PAC-KE80TB-F
PAC-KE04DM-F
PAC-KE89LAF
PAC-KE140TB-F
PAC-KE04DM-F
PAC-KE89LAF
PAC-KE140TB-F
PAC-KE04DM-F
PAC-KE89LAF
PAC-KE140TB-F
PAC-KE04DM-F
O.D. 32mm (1-1/4)
*5 The factory setting of external static pressure is shown without < >.
Refer to "Fan characteristics curves", according to the external static pressure, in DATA BOOK for the usable range of air flow rate.