3-7. Power supply unit [PAC-SC51KUA]
PAC-SC51KUA supplies DC power of M-NET (23-32V) and 24V at TB2 and TB3 respectively; the former is for centralized
transmission use and the latter is for AG-150A operation and LAN function use.
1.
When using PAC-SC51KUA as the power supplier for system controller, the capacity for system controller is
considered as follows.
Main SC
Sub SC
Add : 000
Add: 201
SC: System Controller
Centralized control
transmission line
Indoor/outdoor transmission line
Indoor/outdoor transmission line
CN41
CN41
TB7
TB7
M-NET
Fig.
1
Equivalent power consumption of controllers
In this case, pay attention to leave the power supply switch connector on CN41 of the Outdoor unit as the factory setting
before shipment.
T
aking the power consumption of the control board of Indoor unit as 1, the power consumption of various controllers is rated
at T
able 1.
Centralized controller
System controller
M-NET remote controller
M-NET remote controller
T
able 1
Equivalent power consumption of controllers
PAC-SC51KUA is capable to supply equivalent power up to 5, therefore the maximum connectable number of system controller
is as follows.
*1: According to the system restrictions, PAC-SC51KUA can be connected to only one centralized controller.
As the air conditioner control system may combine all kinds of system controllers, the total power
consumption of system controllers need to count with Table 2.
For example, the controller system contains 1 AG-150A and 2 ON/OFF remote controllers (PAC-YT40ANRA) connected at
centralized control communication line.
Then the total power consumption is
1 x 0.5 + 2 x 1 = 2.5 < 5.
One P
AC-SC51KUA is therefore enough. The total power consumption should not exceed 5.
T
able 2
Max. connectable quianity of controller when using PAC-SC51KUA
0.5
ON/OFF remote controller
(PAC-YT40ANRA)
Advanced touch controller
(AT-50B)
AG-150A
0
AE-200E
AE-50E
ME remote controller
1
4
(PAR-U02MEDA)
ME remote controller
(PAR-U02MEDA)
0.5
System controller
ON/OFF remote controller
(PAC-YT40ANRA)
Advanced touch controller
(AT-50B)
Centralized controller
*1
AG-150A
1unit
1unit
10 units
5 units
PAC-SC51KUA
(TB2 and TB3 used)
24VDC
CAUTION
When applying Charge and/or Peak-cut function on AG-150A, Power Supply Unit (PAC-SC51KUA) is recommended to use.
AG-150A is possible to receive power from one of the Outdoor units, but there is a risk that the failure of power supply from
the Outdoor unit will cause AG-150A's functiondown on the whole system.