Controller
MEE15K022
3. System remote controller
YKB/YLM 2nd
3-9. Integrated centralized control software [TG-2000A]
Main features of TG-2000A
1
2  The air-conditioner layout can be displayed on the screen, making control and operation easier.
3  The annual and weekly schedules can be set. 5 schedules, such as the summer master and winter master, can be  
 
saved in the weekly schedule.
4  Air-conditioning charges can be calculated based on the multiple air-conditioner usage results.
The power apportionment
 
percentage data and apportioned power rate can be calculated for each indoor unit using the power apportionment
 
function, and can be output as a CSV format file.
Charging without WHM
The user manually inputs the power rate to calculate the air-conditioning charges. (Using a tool)
PLC + pulse WHM charging
The pulse output WHM value is automatically tabulated by the PLC to calculate the air-conditioning charges.
5  Energy saving operation is possible using the "ON/OFF", "set temperature change", "fan operation changeover" and
"performance save operation (60% to 90%)" functions.
 Energy saving operation matching the amount of power in use is possible by using the PI controller or PLC's electric amount
count software.
6  Night Set-Back function operation is possible with schedule settings.
7  General equipment can be operated and monitored.
 
8  General equipment can be schedule-controlled when using P
AC-YG21CDA with PLC or DIDO Controller (PAC-YG66DCA).
 
(For details of PLC refer to Installation Manual of PAC-YG21CDA.)
1:
1
Only one of these functions can be used.
2:
3:
 Power apportionment charging is not possible with the old model, A control or K control.
Energy
manag-
ement
Web
monitor
license
Schedule
license
etc.
Input
M-NET
1. Example of Basic System Configuration.
3-phase 208/230V
(3-wire)
Indoor unit system
watt-hour meter
Outdoor unit system
watt-hour meter
PI Controller
(PAC-YG60MCA)
Uninterruptive
power supply (UPS)
Integrated
centralized control
software installation
Centralized controller
personal computer
TG-2000A
Indoor unit
watt-hour meter
Single-phase 208/230V
Single-phase 208/230V
power source
Indoor unit system watt-hour meter
Outdoor unit system watt-hour meter
PLC (with electric amount count software)
Indoor unit watt-hour meter
PLC (PAC-YG11CDA)
The electric amount count software or separately
procured parts must be used with the designated PLC.
The TG-2000A can realize the following functions
using the AE-200E/AE-50E/EW-50E/AG-150A or EB-50GU-J option (license).
Operation/monitor
Annual/weekly schedule
Charge
Energy saving
Peak cut
Note : Depending on the versions of TG-2000A/AE-200E/AE-50E/EW-50E/AG-150A,
 With Night Set-Back function, the CITY MULTI system can run at heating mode with target temperature set to 12°C / 54°F under schedule control.
 (It depends on the outdoor unit model. Not applicable on PUMY
.) This function can protect the room from dropping down to extremely low temperature at mid-night.
AG-150A controls 50 units. When AG-150A is connected with PAC-YG50ECA, units are counted based on the number of connected PAC-YG50ECA.
4:
EB-50GU-J is compatible with TG-2000A  Ver.6.40A or later.
5:
AE-200E/AE-50E is compatible with TG-2000A Ver. 6.50A or later.
6:
EW-50E is compatible with TG-2000A Ver.6.60 or later.
Note: AG-150A is compatible with TG-2000A Ver.5.5* or later. GB-50ADA-J is compatible with TG-2000A Ver. 6.3* or later.
AG-150A connected with PAC-YG50ECA is compatible with TG-2000A Ver.6.1* or later.
Depending on the versions of TG-2000A and AE-200E/AE-50E/EW-50E/AG-150A/EB-50GU-J, some of the functions may not be available
          for use. Each system allows the connection of only one TG-2000A.
and EB-50GU-J, some of the functions may not be available for use.
:
:
  Up to 2000 units (40 AE-200E  
5
/AE-50E  
5
/EW-50E  
6
/AG-150A  
3
 or EB-50GU-J  
4
units) can be operated and monitored simultaneously
.
1
PI controller + pulse WHM charging
:
The pulse output WHM value is automatically tabulated by the PI controller (PAC-YG60MCA) to
calculate the air conditioning charges.
1
2
AE-200E
Power supply unit
PAC-SC51KUA
harmful interference, and (2)this device must accept any interference
received, including interference that may cause undesired operation.
subject to the following two conditions: (1)this device may not cause
This device complies with Part15 of the FCC Rules.Operation is
Dual
Set
Point