Controller
MEE15K022
3. System remote controller
YKB/YLM 2nd
(4) Recommended circuit
(A) Level signal
CN5
X1
X1
9
8
7
6
5
1
EB-50GU
Red
Orange
Max.
10 m (32 ft)
ON/OFF or
Emergency stop
External power
supply
*1
(12 or 24 VDC)
Use relays X1, X2, Y1, and Y2 that meet the following
specifications.
Contact rating
Rated voltage: 12 VDC or above
Rated current: 0.1 A or above
Minimum applied load: DC 1 mA
*1 Select an external power supply suitable for the relays
used. (12 or 24 VDC)
Connect the external power supply in the correct polarity
to input and output the signals.
Connect  5  –  8  (see the figure at left) to the negative
side.
Important
Be sure to use an external power supply (12 or 24
VDC) to avoid malfunctions.
Connect the external power supply in the correct
polarity to avoid malfunctions.
(B) Pulse signal
CN5
X1
X2
Y1
Y2
X1
X2
Y1
Y2
9
8
7
6
5
1
EB-50GU
Red
Gray
Blue
Yellow
Orange
Max.
10 m (32 ft)
External power supply *1 (12 or 24 VDC)
ON
OFF
Prohibit
Permit
Note
The total length of the lead wire and extension cable should not exceed 10 m (32 ft). (Use an extension cable  
of 0.3 mm
2
 or thicker.)
The relays, external power supply, and extension cables are field supplied.
Cut the excess cable near the connector, and insulate the end of unused cable with tape.
(1) External signal output specifications
* The operation status of general equipments (via DIDO controller (PAC-YG66DCA)) will not be output.
* The ON signal will be output even during an error.
[External signal output function]
An ON signal is output when one or more units are in operation, and Error signal is output when one or more units are in error.
CN5
Lead wire from
PAC-YG10HA-E
Signal
No. 1
Green
Common ground for external output (Ground for external power supply)
No. 2
Black
ON signal*, OFF signal
No. 3
Brown
Error signal, Normal signal
(2) Recommended circuit
Relay-driven circuit
CN5
4
9
3
2
1
Z1
L1
Z2
L2
Z1
Z2
EB-50GU
Brown
Diode
*2
Max.
10 m (32 ft)
L1: ON indicator
L2: Error indicator
External power supply
*1
Black
Green
Use relays Z1 and Z2 that meet the following specifications.
Operation coil
Rated voltage: 12 or 24 VDC
Power consumption: Max. 0.9 W
*1 Select an external power supply suitable for the relays used.
     (12 or 24 VDC)
Connect the external power supply in the correct polarity to
input and output the signals.
*2 Use a diode at both ends of the relay coils.
Important
Be sure to use an external power supply (12 or 24VDC)
to avoid malfunctions.
Connect the external power supply in the correct polarity
to avoid malfunctions.
Do not connect the external power supply without relays
being connected to the controller (no load).
Note
The relays, lamps, external power supply, diodes, and extension cables are field supplied.
The total length of the lead wire and extension cable should not exceed 10 m (32 ft). (Use an extension cable of 0.3
mm
2
 or thicker.)
Each element will turn on during operation and when an error occurs.
Connect      (shown in the figure at left) to the negative side.
1