Controller
MEE15K022
3. System remote controller
YKB/YLM 2nd
(1)
Setting example for connecting multiple M-NET system controllers
EB-50GU
[000]
[201]
M-NET
(Main system controller)
ON/OFF remote controller
(Sub system controller)
PC
HUB
LAN
50 indoor units
LAN
Make the initial settings such as group settings and interlock settings on the Web browser. Refer to the Instruction
Book (Web Browser for Initial Settings) for details.
Designate a system controller within the system as the only controller from which operation prohibit setting can be
made.
(2)
Setting example for controlling Mr. Slim units (M-series/P-series models)
EB-50GU
[000]
PC
(Main system controller)
LAN
HUB
20 indoor units
Groups 1–20
Mr. Slim outdoor units
Groups 21 and 22
2 M-NET adapters
(adapter address 21 and 22)
LAN
An M-NET adapter (sold separately) is required to connect the Mr. Slim model of units to the M-NET
.
2. M-NET system setting example
3. External input/output
To use external input/output, a separately-sold external input/output adapter (P
AC-YG10HA-E) and external power
supply (12 or 24 VDC) are required.
External input/output terminal (CN5)
(1) External signal input function setting
Setting mode
Description
Not in use (Factory setting)
External input signal will not be used.
Emergency Stop (Level signal)
Using a level signal, all the air conditioning units connected to the EB-50GU will
be stopped collectively in emergency. During an emergency stop, the ON/OFF
operation from the local remote controllers will be prohibited, and the ON/OFF
operation and Prohibit/Permit settings on the EB-50GU will be prohibited.
Scheduled operations will not be performed.
ON/OFF (Level signal)
Using a level signal, all the air conditioning units connected to the EB-50GU will
be run or stopped collectively. The ON/OFF operation from the local remote
controllers will be prohibited, and the ON/OFF operation and Prohibit/Permit
settings on the EB-50GU will be prohibited. Scheduled operations will not be performed.
ON/OFF/Prohibit/Permit (Pulse signal)
Using a pulse signal, all the air conditioning units connected to the EB-50GU will be
run or stopped collectively, or the operation from the local remote controllers will
be prohibited or permitted collectively.
* General equipments connected via DIDO controller (PAC-YG66DCA) cannot be collectively run or stopped by using the external signal
input function unless [Emergency Stop (Level signal)] is selected and relevant switches on the DIDO controller are set.
[External signal input function]
Using external contact signals (12 or 24 VDC), the following collective operations for all connected air conditioning units can
be controlled: Emergency stop, ON/OFF operation, and Prohibit/Permit local remote controller operation.