1. SPECIFICATIONS
DATA G10
OUTDOOR UNITS
2 - 32
Y
 Model
PUHY-P400YJM-A(-BS)
PUHY-P450YJM-A(-BS)
Power source
3-phase 4-wire 380-400-415V 50/60Hz
3-phase 4-wire 380-400-415V 50/60Hz
 Cooling capacity
*1
kW
45.0
50.0
(Nominal)
*1
kcal / h
38,700
43,000
*1
BTU / h
153,500
170,600
Power input
kW
13.11
15.47
Current input
A
22.1-21.0-20.2
26.1-24.8-23.9
COP
kW / kW
3.43
3.23
 Temp. range of
Indoor
W.
B.
15.0~24.0°C(59~75°F)
15.0~24.0°C(59~75°F)
 cooling
Outdoor
D.B.
-5.0~46.0°C(23~115°F)
-5.0~46.0°C(23~115°F)
 Heating capacity
*2
kW
50.0
56.0
(Nominal)
*2
kcal / h
43,000
48,200
*2
BTU / h
170,600
191,100
Power input
kW
12.82
14.62
Current input
A
21.6-20.5-19.8
24.6-23.4-22.5
COP
kW / kW
3.90
3.83
 Temp. range of
Indoor
D.
B.
15.0~27.0°C(59~81°F)
15.0~27.0°C(59~81°F)
 heating
Outdoor
W.B.
-20.0~15.5°C(-4~60°F)
-20.0~15.5°C(-4~60°F)
Indoor unit
Total capacity
50~130 % of outdoor unit capacity
50~130 % of outdoor unit capacity
connectable
Model / Quantity
P15~P250 / 1~34
P15~P250 / 1~39
 Sound pressure level (measured in anechoic room)
dB <A>
61
62
Power pressure level (measured in anechoic room)
dB <A>
81
82
Refrigerant
Liquid pipe
mm (in.)
12.7(1/2) Brazed
15.88(5/8) Brazed
piping diameter
Gas pipe
mm (in.)
28.58(1-1/8) Brazed
28.58(1-1/8) Brazed
FAN
Type x Quantity
Propeller fan x 1
Propeller fan x 2
Air flow rate
m
3
 / min
210
370
L/s
3,500
6,167
cfm
7,415
13,065
Control, Driving mechanism
Inverter-control, Direct-driven by motor
Inverter-control, Direct-driven by motor
Motor output
kW
0.46 x 1
0.46 x 2
*3
External static press.
0 Pa (0 mmH
2
O)
0 Pa (0 mmH
2
O)
Compressor
Type x Quantity
Inverter scroll hermetic compressor
Inverter scroll hermetic compressor
Manufacture
AC&R Works, MITSUBISHI ELECTRIC CORPORATION
AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method
Inverter
Inverter
Motor output
kW
10.1
11.6
Case heater
kW
0.045
0.045
Lubricant
MEL32
MEL32
 External finish
Pre-coated galvanized steel sheets (+powder coating for -BS
type)
Pre-coated galvanized steel sheets (+powder coating for -BS
type)
<MUNSELL 5Y 8/1 or similar>
<MUNSELL 5Y 8/1 or similar>
External dimension HxWxD
mm
1,710(1,650 without legs) x 1,220 x 760
1,710(1,650 without legs) x 1,750 x 760
in.
67-3/8(65 without legs) x 48-1/16 x 29-15/16
67-3/8(65 without legs) x 68-15/16 x 29-15/16
Protection  devices
High pressure protection
High pressure sensor, High pressure switch at 4.15MPa (601
psi)
High pressure sensor, High pressure switch at 4.15MPa (601
psi)
Inverter circuit (COMP. / FAN)
Over-heat protection, Over-current protection
Over-heat protection, Over-current protection
Compressor
Over-heat protection
Over-heat protection
Fan motor
Thermal switch
Thermal switch
Refrigerant
Type x original charge
R410A x 11.5kg (26lbs)
R410A x 11.8kg (27lbs)
Control
LEV and HIC circuit
LEV and HIC circuit
Net weight
kg (lbs)
250(552)
290(640)
Heat exchanger
Salt-resistant cross fin & copper tube
Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer)
Copper pipe,tube-in-tube structure
Copper pipe,tube-in-tube structure
Defrosting method
Auto-defrost mode (Reversed refrigerant cycle)
Auto-defrost mode (Reversed refrigerant cycle)
 Drawing
External
WKD94G063
WKD94G064
Wiring
KE94C449
KE94C450
Standard attachment
Document
Installation Manual
Installation Manual
Accessory
Refrigerant conn. pipe
Refrigerant conn. pipe
 Optional parts
Joint: CMY-Y102SS/LS-G2, CMY-Y202S-G2
Joint: CMY-Y102SS/LS-G2, CMY-Y202S-G2
Header: CMY-Y104/108/1010-G
Header: CMY-Y104/108/1010-G
Remarks
Details on foundation work, duct work, insulation work, electri-
cal wiring, power source switch, and other items shall be re-
ferred to the Installation Manual.
Due to continuing improvement, above specifications may be
subject to change without notice.
Details on foundation work, duct work, insulation work, electri-
cal wiring, power source switch, and other items shall be re-
ferred to the Installation Manual.
Due to continuing improvement, above specifications may be
subject to change without notice.
Notes :
Unit converter
1.Nominal cooling conditions(subject to JIS B8615-2)
   Indoor:27°CDB/19°CWB(81°FDB/66°FWB), Outdoor:35°CDB(95°FDB)
   Pipe length:7.5m(24-9/16ft.
), Level difference:0m(0ft.)
 2.Nominal heating conditions(subject to JIS B8615-2)
   Indoor:20°CDB(68°FDB), Outdoor:7°CDB/6°CWB(45°FDB/43°FWB)
   Pipe length:7.5m(24-9/16ft.
), Level difference:0m(0ft.)
 3.External static pressure option is available (30Pa, 60Pa / 3.1mmH
2
O, 6.1mmH
2
O).
  kcal
=kW x 860
  BTU/h
=kW x 3,412
  cfm
=m
3
/min x 35.31
  lbs
=kg / 0.4536
 *Above specification data is
 subject to rounding variation.