1. SPECIFICATIONS
DATA G10
OUTDOOR UNITS
Y
 Model
PUHY-P300YJM-A(-BS)
PUHY-P350YJM-A(-BS)
 Power source
3-phase 4-wire 380-400-415V 50/60Hz
3-phase 4-wire 380-400-415V 50/60Hz
 Cooling capacity
*1
kW
33.5
40.0
 (Nominal)
*1
kcal / h
28,800
34,400
*1
BTU / h
114,300
136,500
Power input
kW
9.00
11.01
Current input
A
15.1-14.4-13.9
18.5-17.6-17.0
COP
kW / kW
3.72
3.63
 Temp.
 range of
Indoor
W.
B.
15.0~24.0°C(59~75°F)
15.0~24.0°C(59~75°F)
 cooling
Outdoor
D.
B.
-5.0~46.0°C(23~115°F)
-5.0~46.0°C(23~115°F)
 Heating capacity
*2
kW
37.5
45.0
 (Nominal)
*2
kcal / h
32,300
38,700
*2
BTU / h
128,000
153,500
Power input
kW
9.25
11.19
Current input
A
15.6-14.8-14.2
18.8-17.9-17.2
COP
kW / kW
4.05
4.02
 Temp.
 range of
Indoor
D.
B.
15.0~27.0°C(59~81°F)
15.0~27.0°C(59~81°F)
 heating
Outdoor
W.B.
-20.0~15.5°C(-4~60°F)
-20.0~15.5°C(-4~60°F)
 Indoor unit
Total capacity
50~130 % of outdoor unit capacity
50~130 % of outdoor unit capacity
 connectable
Model / Quantity
P15~P250 / 1~26
P15~P250 / 1~30
 Sound pressure level (measured in anechoic room)
dB <A>
59
60
 Power pressure level (measured in anechoic room)
dB <A>
79
80
 Refrigerant
Liquid pipe
mm (in.
)
9.52(3/8) Brazed (12.7(1/2) Brazed,total length >= 40m)
12.7(1/2) Brazed
piping diameter
Gas pipe
mm (in.
)
22.2(7/8) Brazed
28.58(1-1/8) Brazed
 FAN
Type x Quantity
Propeller fan x 1
Propeller fan x 1
Air flow rate
m
3
 / min
170
210
L/s
2,833
3,500
cfm
6,003
7,415
Control, Driving mechanism
Inverter-control, Direct-driven by motor
Inverter-control, Direct-driven by motor
Motor output
kW
0.46 x 1
0.46 x 1
*3
External static press.
0 Pa (0 mmH
2
O)
0 Pa (0 mmH
2
O)
 Compressor
Type x Quantity
Inverter scroll hermetic compressor
Inverter scroll hermetic compressor
Manufacture
AC&R Works, MITSUBISHI ELECTRIC CORPORATION
AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method
Inverter
Inverter
Motor output
kW
7.7
9.9
Case heater
kW
0.045
0.045
Lubricant
MEL32
MEL32
 External finish
Pre-coated galvanized steel sheets (+powder coating for -BS
type)
Pre-coated galvanized steel sheets (+powder coating for -BS
type)
<MUNSELL 5Y 8/1 or similar>
<MUNSELL 5Y 8/1 or similar>
 External dimension HxWxD
mm
1,710(1,650 without legs) x 920 x 760
1,710(1,650 without legs) x 1,220 x 760
in.
67-3/8(65 without legs) x 36-1/4 x 29-15/16
67-3/8(65 without legs) x 48-1/16 x 29-15/16
 Protection  devices
High pressure protection
High pressure sensor, High pressure switch at 4.15MPa (601
psi)
High pressure sensor, High pressure switch at 4.15MPa (601
psi)
Inverter circuit (COMP. / FAN)
Over-heat protection, Over-current protection
Over-heat protection, Over-current protection
Compressor
Over-heat protection
Over-heat protection
Fan motor
Thermal switch
Thermal switch
 Refrigerant
Type x original charge
R410A x 8.0kg (18lbs)
R410A x 11.5kg (26lbs)
Control
LEV and HIC circuit
LEV and HIC circuit
 Net weight
kg (lbs)
215(474)
250(552)
 Heat exchanger
Salt-resistant cross fin & copper tube
Salt-resistant cross fin & copper tube
 HIC circuit (HIC: Heat Inter-Changer)
Copper pipe,tube-in-tube structure
Copper pipe,tube-in-tube structure
 Defrosting method
Auto-defrost mode (Reversed refrigerant cycle)
Auto-defrost mode (Reversed refrigerant cycle)
 Drawing
External
WKD94G062
WKD94G063
Wiring
KE94C449
KE94C449
 Standard attachment
Document
Installation Manual
Installation Manual
Accessory
Refrigerant conn. pipe
Refrigerant conn. pipe
 Optional parts
Joint: CMY-Y102SS/LS-G2
Joint: CMY-Y102SS/LS-G2, CMY-Y202S-G2
Header: CMY-Y104/108/1010-G
Header: CMY-Y104/108/1010-G
Remarks
Details on foundation work, duct work, insulation work, electri-
cal wiring, power source switch, and other items shall be re-
ferred to the Installation Manual.
Due to continuing improvement, above specifications may be
subject to change without notice.
Details on foundation work, duct work, insulation work, electri-
cal wiring, power source switch, and other items shall be re-
ferred to the Installation Manual.
Due to continuing improvement, above specifications may be
subject to change without notice.
Notes :
Unit converter
 1.Nominal cooling conditions(subject to JIS B8615-2)
 Indoor:27°CDB/19°CWB(81°FDB/66°FWB), Outdoor:35°CDB(95°FDB)
 Pipe length:7.5m(24-9/16ft.), Level difference:0m(0ft.)
  2.Nominal heating conditions(subject to JIS B8615-2)
 Indoor:20°CDB(68°FDB), Outdoor:7°CDB/6°CWB(45°FDB/43°FWB)
 Pipe length:7.5m(24-9/16ft.), Level difference:0m(0ft.)
  3.External static pressure option is available (30Pa, 60Pa / 3.1mmH
2
O, 6.1mmH
2
O).
kcal
=kW x 860
  BTU/h
=kW x 3,412
cfm
=m
3
/min x 35.31
lbs
=kg / 0.4536
 *Above specification data is
 subject to rounding variation.