1 2 3 4 5 6 7 8 9 10 11 .. 86
1. SPECIFICATIONS
DATA G10
OUTDOOR UNITS
2 - 30
Y
I.
Y SERIES
1. SPECIFICATIONS
 Model
PUHY-P200YJM-A(-BS)
PUHY-P250YJM-A(-BS)
Power source
3-phase 4-wire 380-400-415V 50/60Hz
3-phase 4-wire 380-400-415V 50/60Hz
 Cooling capacity
*1
kW
22.4
28.0
(Nominal)
*1
kcal / h
19,300
24,100
*1
BTU / h
76,400
95,500
Power input
kW
5.62
7.40
Current input
A
9.4-9.0-8.6
12.4-11.8-11.4
COP
kW / kW
3.98
3.78
 Temp. range of
Indoor
W.
B.
15.0~24.0°C(59~75°F)
15.0~24.0°C(59~75°F)
 cooling
Outdoor
D.B.
-5.0~46.0°C(23~115°F)
-5.0~46.0°C(23~115°F)
 Heating capacity
*2
kW
25.0
31.5
(Nominal)
*2
kcal / h
21,500
27,100
*2
BTU / h
85,300
107,500
Power input
kW
5.84
7.34
Current input
A
9.8-9.3-9.0
12.3-11.7-11.3
COP
kW / kW
4.28
4.29
 Temp. range of
Indoor
D.
B.
15.0~27.0°C(59~81°F)
15.0~27.0°C(59~81°F)
 heating
Outdoor
W.B.
-20.0~15.5°C(-4~60°F)
-20.0~15.5°C(-4~60°F)
Indoor unit
Total capacity
50~130 % of outdoor unit capacity
50~130 % of outdoor unit capacity
connectable
Model / Quantity
P15~P250 / 1~17
P15~P250 / 1~21
 Sound pressure level (measured in anechoic room)
dB <A>
56
58
Power pressure level (measured in anechoic room)
dB <A>
76
78
Refrigerant
Liquid pipe
mm (in.)
9.52(3/8) Brazed
9.52(3/8) Brazed (12.7(1/2) Brazed,total length >= 90m)
piping diameter
Gas pipe
mm (in.)
19.05(3/4) Brazed
22.2(7/8) Brazed
FAN
Type x Quantity
Propeller fan x 1
Propeller fan x 1
Air flow rate
m
3
 / min
170
170
L/s
2,833
2,833
cfm
6,003
6,003
Control, Driving mechanism
Inverter-control, Direct-driven by motor
Inverter-control, Direct-driven by motor
Motor output
kW
0.46 x 1
0.46 x 1
*3
External static press.
0 Pa (0 mmH
2
O)
0 Pa (0 mmH
2
O)
Compressor
Type x Quantity
Inverter scroll hermetic compressor
Inverter scroll hermetic compressor
Manufacture
AC&R Works, MITSUBISHI ELECTRIC CORPORATION
AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method
Inverter
Inverter
Motor output
kW
5.4
6.8
Case heater
kW
0.035
0.035
Lubricant
MEL32
MEL32
 External finish
Pre-coated galvanized steel sheets (+powder coating for -BS
type)
Pre-coated galvanized steel sheets (+powder coating for -BS
type)
<MUNSELL 5Y 8/1 or similar>
<MUNSELL 5Y 8/1 or similar>
External dimension HxWxD
mm
1,710(1,650 without legs) x 920 x 760
1,710(1,650 without legs) x 920 x 760
in.
67-3/8(65 without legs) x 36-1/4 x 29-15/16
67-3/8(65 without legs) x 36-1/4 x 29-15/16
Protection  devices
High pressure protection
High pressure sensor, High pressure switch at 4.15MPa (601
psi)
High pressure sensor, High pressure switch at 4.15MPa (601
psi)
Inverter circuit (COMP. / FAN)
Over-heat protection, Over-current protection
Over-heat protection, Over-current protection
Compressor
Over-heat protection
Over-heat protection
Fan motor
Thermal switch
Thermal switch
Refrigerant
Type x original charge
R410A x 6.5kg (15lbs)
R410A x 8.0kg (18lbs)
Control
LEV and HIC circuit
LEV and HIC circuit
Net weight
kg (lbs)
190(419)
200(441)
Heat exchanger
Salt-resistant cross fin & copper tube
Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer)
Copper pipe,tube-in-tube structure
Copper pipe,tube-in-tube structure
Defrosting method
Auto-defrost mode (Reversed refrigerant cycle)
Auto-defrost mode (Reversed refrigerant cycle)
 Drawing
External
WKD94G062
WKD94G062
Wiring
KE94C449
KE94C449
Standard attachment
Document
Installation Manual
Installation Manual
Accessory
Refrigerant conn. pipe
Refrigerant conn. pipe
 Optional parts
Joint: CMY-Y102SS-G2
Joint: CMY-Y102SS/LS-G2
Header: CMY-Y104/108/1010-G
Header: CMY-Y104/108/1010-G
Remarks
Details on foundation work, duct work, insulation work, electri-
cal wiring, power source switch, and other items shall be re-
ferred to the Installation Manual.
Due to continuing improvement, above specifications may be
subject to change without notice.
Details on foundation work, duct work, insulation work, electri-
cal wiring, power source switch, and other items shall be re-
ferred to the Installation Manual.
Due to continuing improvement, above specifications may be
subject to change without notice.
Notes :
Unit converter
1.Nominal cooling conditions(subject to JIS B8615-2)
   Indoor:27°CDB/19°CWB(81°FDB/66°FWB), Outdoor:35°CDB(95°FDB)
   Pipe length:7.5m(24-9/16ft.
), Level difference:0m(0ft.)
 2.Nominal heating conditions(subject to JIS B8615-2)
   Indoor:20°CDB(68°FDB), Outdoor:7°CDB/6°CWB(45°FDB/43°FWB)
   Pipe length:7.5m(24-9/16ft.
), Level difference:0m(0ft.)
 3.External static pressure option is available (30Pa, 60Pa / 3.1mmH
2
O, 6.1mmH
2
O).
  kcal
=kW x 860
  BTU/h
=kW x 3,412
  cfm
=m
3
/min x 35.31
  lbs
=kg / 0.4536
 *Above specification data is
 subject to rounding variation.