1. SPECIFICATIONS
DATA G10
2 - 13
OUTDOOR UNITS
S
 Model
PUMY-P140VHMB
 Power source
1-phase 220-230-240V 50Hz / 1-phase 220V 60Hz
 Cooling capacity
*1
kW
15.5
 (Nominal)
*1
kcal / h
13,300
*1
BTU / h
52,900
Power input
kW
5.35
Current input
A
24.7-23.6-22.7 / 24.7
COP
kW / kW
2.9
 Temp. range of
Indoor
W.
B.
15 to 24degC(59 to 75degF)
 cooling
Outdoor
D.B.
-5 to 46degC(23 to 115degF)
10 to 46degC(50 to 115degF) : in case of connecting
PKFY-P15/P20/P25 type indoor unit.
 Heating capacity
*2
kW
18.0
 (Nominal)
*2
kcal / h
15,500
*2
BTU / h
61,400
Power input
kW
5.58
Current input
A
25.8-24.7-23.6 / 25.8
COP
kW / kW
3.23
 Temp. range of
Indoor
D.
B.
15 to 27degC(59 to 81degF)
 heating
Outdoor
W.B.
-15 to 15degC(5 to 59degF)
 Indoor unit
Total capacity
50 to 130 % of outdoor unit capacity
 connectable
Model / Quantity
P15 to P140 / 1 to 12
 Sound pressure level (measured in anechoic room)
dB <A>
51 / 53
 Refrigerant
Liquid pipe
 mm(in.)
9.52(3/8)
piping diameter
Gas pipe
mm(in.)
15.88(5/8)
 FAN
Type x Quantity
Propeller fan x 2
Air flow rate
m
3
 / min
100
L/s
1,667
cfm
3,532
Control, Driving mechanism
DC-control, Direct-driven by motor
Motor output
 kW
0.06 x 2
External static press.
0 Pa (0 mmH
2
O)
 Compressor
Type x Quantity
Inverter scroll hermetic compressor
Manufacture
MITSUBISHI ELECTRIC CORPORATION
Starting method
Inverter
Motor output
 kW
3.3
Case heater
kW
-
Lubricant
FV50S x 2.3L
 External finish
Galvanized steel sheets
<MUNSELL 3Y 7.8/1.1>
 External dimension HxWxD
 mm
1,350 x 950 x 330
 in.
53-3/16 x 37-7/16 x 13
 Protection devices
High pressure protection
High pressure sensor, High pressure switch at 4.15MPa (601
psi)
Inverter circuit (COMP. / FAN)
Over-heat protection,Over-current protection
Compressor
Compressor thermo protection,Over-current protection
Fan motor
Over-heat protection,Voltage protection
 Refrigerant
Type x original charge
R410A x 8.5kg (19lbs)
Control
LEV circuit
 Net weight
 kg(lbs)
129(284)
 Heat exchanger
Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer)
-
 Defrosting method
Auto-defrost mode (Reversed refrigerant cycle)
 Drawing
External
VHM-BK01-B434
Wiring
VHM-RG79-V708
 Standard attachment
Document
Installation Manual
Accessory
Grounded lead wire x 2
 Optional parts
Joint: CMY-Y62-G-E
Header: CMY-Y64/68-G-E
 Remarks
* In case of connecting Fresh air intake type indoor unit PEFY-P-VHM-E-F, only one indoor unit can be connected with one
PUMY.
 
* Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be re-
ferred to the Installation Manual.
* Due to continuing improvement, above specifications may be subject to change without notice.
Notes :
Unit converter
 *1.Nominal cooling conditions(subject to JIS B8615-1)
kcal
=kW x 860
 Indoor : 27degCDB/19degCWB(81degFDB/66degFWB), Outdoor : 35degCDB(95degFDB)
BTU/h
=kW x 3,412
 Pipe length : 7.5m(24-9/16ft.
), Level difference : 0m(0ft.)
cfm
=m
3
/min x 35.31
 *2.Nominal heating conditions(subject to JIS B8615-1)
lbs
=kg / 0.4536
 Indoor : 20degCDB(68degFDB), Outdoor : 7degCDB/6degCWB(45degFDB/43degFWB)
 Pipe length : 7.5m(24-9/16ft.
), Level difference : 0m(0ft.)