1. SPECIFICATIONS
DATA G10
OUTDOOR UNITS
2 - 12
S
 Model
PUMY-P100VHMB
PUMY-P125VHMB
Power source
1-phase 220-230-240V 50Hz / 1-phase 220V 60Hz
1-phase 220-230-240V 50Hz / 1-phase 220V 60Hz
 Cooling capacity
*1
kW
11.2
14.0
(Nominal)
*1
kcal / h
9,600
12,000
*1
BTU / h
38,200
47,800
Power input
kW
3.34
4.32
Current input
A
15.4-14.8-14.1 / 15.4
20.0-19.1-18.3 / 20.0
COP
kW / kW
3.35
3.24
Temp. range of
Indoor
W.
B.
15 to 24degC(59 to 75degF)
15 to 24degC(59 to 75degF)
cooling
Outdoor
D.
B.
-5 to 46degC(23 to 115degF)
-5 to 46degC(23 to 115degF)
10 to 46degC(50 to 115degF) : in case of connecting
PKFY-P15/P20/P25 type indoor unit.
10 to 46degC(50 to 115degF) : in case of connecting
PKFY-P15/P20/P25 type indoor unit.
 Heating capacity
*2
kW
12.5
16.0
(Nominal)
*2
kcal / h
10,800
13,800
*2
BTU / h
42,700
54,600
Power input
kW
3.66
4.33
Current input
A
16.9-16.2-15.5 / 16.9
20.0-19.1-18.3 / 20.0
COP
kW / kW
3.42
3.69
Temp. range of
Indoor
D.
B.
15 to 27degC(59 to 81degF)
15 to 27degC(59 to 81degF)
heating
Outdoor
W.B.
-15 to 15degC(5 to 59degF)
-15 to 15degC(5 to 59degF)
Indoor unit
Total capacity
50 to 130 % of outdoor unit capacity
50 to 130 % of outdoor unit capacity
connectable
Model / Quantity
P15 to P125 / 1 to 8
P15 to P140 / 1 to 10
 Sound pressure level (measured in anechoic room)
dB <A>
49 / 51
50 / 52
 Refrigerant
Liquid pipe
 mm(in.)
9.52(3/8)
9.52(3/8)
piping diameter
Gas pipe
mm(in.)
15.88(5/8)
15.88(5/8)
FAN
Type x Quantity
Propeller fan x 2
Propeller fan x 2
Air flow rate
m
3
 / min
100
100
L/s
1,667
1,667
cfm
3,532
3,532
Control, Driving mechanism
DC-control, Direct-driven by motor
DC-control, Direct-driven by motor
Motor output
kW
0.06 x 2
0.06 x 2
External static press.
0 Pa (0 mmH
2
O)
0 Pa (0 mmH
2
O)
Compressor
Type x Quantity
Inverter scroll hermetic compressor
Inverter scroll hermetic compressor
Manufacture
MITSUBISHI ELECTRIC CORPORATION
MITSUBISHI ELECTRIC CORPORATION
Starting method
Inverter
Inverter
Motor output
kW
2.2
2.9
Case heater
kW
-
-
Lubricant
FV50S x 2.3L
FV50S x 2.3L
 External finish
Galvanized steel sheets
Galvanized steel sheets
<MUNSELL 3Y 7.8/1.1>
<MUNSELL 3Y 7.8/1.1>
External dimension HxWxD
mm
1,350 x 950 x 330
1,350 x 950 x 330
in.
53-3/16 x 37-7/16 x 13
53-3/16 x 37-7/16 x 13
Protection devices
High pressure protection
High pressure sensor, High pressure switch at 4.15MPa (601
psi)
High pressure sensor, High pressure switch at 4.15MPa (601
psi)
Inverter circuit (COMP.
 / FAN)
Over-heat protection,Over-current protection
Over-heat protection,Over-current protection
Compressor
Compressor thermo protection,Over-current protection
Compressor thermo protection,Over-current protection
Fan motor
Over-heat protection,Voltage protection
Over-heat protection,Voltage protection
Refrigerant
Type x original charge
R410A x 8.5kg (19lbs)
R410A x 8.5kg (19lbs)
Control
LEV circuit
LEV circuit
 Net weight
 kg(lbs)
129(284)
129(284)
Heat exchanger
Salt-resistant cross fin & copper tube
Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer)
-
-
Defrosting method
Auto-defrost mode (Reversed refrigerant cycle)
Auto-defrost mode (Reversed refrigerant cycle)
 Drawing
External
VHM-BK01-B434
VHM-BK01-B434
Wiring
VHM-RG79-V708
VHM-RG79-V708
Standard attachment
Document
Installation Manual
Installation Manual
Accessory
Grounded lead wire x 2
Grounded lead wire x 2
 Optional parts
Joint: CMY-Y62-G-E
Joint: CMY-Y62-G-E
Header: CMY-Y64/68-G-E
Header: CMY-Y64/68-G-E
Remarks
* In case of connecting Fresh air intake type indoor unit PEFY-P-VHM-E-F, only one indoor unit can be connected with one
PUMY.
* Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be re-
ferred to the Installation Manual.
* Due to continuing improvement, above specifications may be subject to change without notice.
Notes :
Unit converter
*1.Nominal cooling conditions(subject to JIS B8615-1)
  kcal
=kW x 860
   Indoor : 27degCDB/19degCWB(81degFDB/66degFWB), Outdoor : 35degCDB(95degFDB)
BTU/h
=kW x 3,412
   Pipe length : 7.5m(24-9/16ft.), Level difference : 0m(0ft.)
  cfm
=m
3
/min x 35.31
*2.Nominal heating conditions(subject to JIS B8615-1)
  lbs
=kg / 0.4536
   Indoor : 20degCDB(68degFDB), Outdoor : 7degCDB/6degCWB(45degFDB/43degFWB)
   Pipe length : 7.5m(24-9/16ft.), Level difference : 0m(0ft.)
 *Above specification data is