1 2 3 4 5 6 7 8 9 10 11 .. 19
1. SPECIFICATIONS
DATA G10
2 - 11
OUTDOOR UNITS
S
 Model
PUMY-P140YHMB
 Power source
3-phase 4-wire 380-400-415V 50Hz
 Cooling capacity
*1
kW
15.5
 (Nominal)
*1
kcal / h
13,300
*1
BTU / h
52,900
Power input
kW
5.32
Current input
A
8.51-8.09-7.80
COP
kW / kW
2.91
 Temp. range of
Indoor
W.
B.
15 to 24degC(59 to 75degF)
 cooling
Outdoor
D.B.
-5 to 46degC(23 to 115degF)
10 to 46degC(50 to 115degF) : in case of connecting
PKFY-P15/P20/P25 type indoor unit.
 Heating capacity
*2
kW
18.0
 (Nominal)
*2
kcal / h
15,500
*2
BTU / h
61,400
Power input
kW
5.32
Current input
A
8.51-8.09-7.80
COP
kW / kW
3.38
 Temp. range of
Indoor
D.
B.
15 to 27degC(59 to 81degF)
 heating
Outdoor
W.B.
-15 to 15degC(5 to 59degF)
 Indoor unit
Total capacity
50 to 130 % of outdoor unit capacity
 connectable
Model / Quantity
P15 to P140 / 1 to 12
 Sound pressure level (measured in anechoic room)
dB <A>
51 / 53
 Refrigerant
Liquid pipe
 mm(in.)
9.52(3/8) Flare
 piping diameter
Gas pipe
 mm(in.)
15.88(5/8) Flare
 FAN
Type x Quantity
Propeller fan x 2
Air flow rate
m
3
 / min
100
L/s
1,667
cfm
3,532
Control, Driving mechanism
DC-control, Direct-driven by motor
Motor output
 kW
0.06 x 2
External static press.
0 Pa (0 mmH
2
O)
 Compressor
Type x Quantity
Inverter scroll hermetic compressor
Manufacture
MITSUBISHI ELECTRIC CORPORATION
Starting method
Inverter
Motor output
 kW
2.9
Case heater
kW
-
Lubricant
FV50S
 External finish
Galvanized steel sheets
<MUNSELL 3Y 7.8/1.1>
 External dimension HxWxD
 mm
1,350 x 950 x 330
 in.
53-3/16 x 37-7/16 x 13
 Protection devices
High pressure protection
High pressure sensor, High pressure switch at 4.15MPa (601
psi)
Inverter circuit (COMP. / FAN)
Over-heat protection,Over-current protection
Compressor
Compressor thermo protection,Over-current protection
Fan motor
Over-heat protection,Voltage protection
 Refrigerant
Type x original charge
R410A x 8.5kg (19lbs)
Control
LEV circuit
 Net weight
 kg(lbs)
142(312)
 Heat exchanger
Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer)
-
 Defrosting method
Auto-defrost mode (Reversed refrigerant cycle)
 Drawing
External
YHM-BK01-B328
Wiring
YHM-RG79-V705
 Standard attachment
Document
Installation Manual
Accessory
Grounded lead wire x 2
 Optional parts
Joint: CMY-Y62-G-E
Header: CMY-Y64/68-G-E
 Remarks
* Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be re-
ferred to the Installation Manual.
* Due to continuing improvement, above specifications may be subject to change without notice.
Notes :
Unit converter
 *1.Nominal cooling conditions(subject to JIS B8615-1)
kcal
=kW x 860
 Indoor : 27degCDB/19degCWB(81degFDB/66degFWB), Outdoor : 35degCDB(95degFDB)
BTU/h
=kW x 3,412
 Pipe length : 7.5m(24-9/16ft.
), Level difference : 0m(0ft.)
cfm
=m
3
/min x 35.31
 *2.Nominal heating conditions(subject to JIS B8615-1)
lbs
=kg / 0.4536
 Indoor : 20degCDB(68degFDB), Outdoor : 7degCDB/6degCWB(45degFDB/43degFWB)
 Pipe length : 7.5m(24-9/16ft.
), Level difference : 0m(0ft.)
 *Above specification data is
subject to rounding variation.