2. M-NET control
YKB/YLM 2nd
4 - 88
S.D. R2
MEE15K022
2. Address should be set to Indoor units, LOSSNAY and system controller.
3. M-NET power is supplied by the Outdoor unit at TB3, while Indoor unit and ME remote controller consume the M-NET power for transmission
    use. The power balance is needed to consider for long M-NET wiring. Details refer to
2-3 "System configuration restrictions".
 
NOTE:
1. Outdoor units OC and OS in one refrigerant circuit system are automatically detected.
    OC and OS are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order
    of their address.
*2 System controller should connect to TB7 at Outdoor and use power supply unit together in Multi-Refrigerant-System.
     For AG-150A, 24VDC should be used with the PAC-SC51KUA.
     For AE-200E, AE-50E, and EW-50E the power supply unit PAC-SC51KUA is unused.
*3 When multiple system controllers are connected in the system, set the controller with more functions than others as a "main"
     controller and others as "sub".
     AE-200E, AE-50E, EW-50E, BAC-HD150, and LM-AP are for exclusive use as a "main" system controller and cannot be used as a “sub”
     system controller.
     Make the setting to only one of the system controllers for "prohibition of operation from local remote controller".
*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
*4 The power supply unit is not necessary for AE-200E, AE-50E, EW-50E, BAC-HD150, and LM-AP.
4. Indoor units should be set with a branch number.
5. Assign an address to each of the sub BC controllers which equals the sum of the smallest address of the indoor units that are
    connected to each sub BC controller and 50.
6. When a PAR-31MAA(E) is connected to a group, no other MA remote controllers can be connected to the same group.
2-4-3-3. MA remote controller, Multi-refrigerant-system, System Controller at TB7/TB3 side, Booster for long M-NET wiring
Indoor unit
MA R/C
MA R/C
(Main)
(Sub)
MA R/C
SRU
Wireless R/C
*1
*1
01
BC controller
53
BC controller
(Main)
93
02
03
30
TB15
TB5
TB02
TB5
TB5
TB2
Transmission Booster
PAC-SF46EPA
TB5
TB15
TB15
TB3
TB15
MA R/C
(Main)
(Sub)
MA R/C
TB15
Indoor unit
ME R/C
MA R/C
LOSSNAY
remote
controller
SRU
Wireless R/C
*1
*1
142
*2, *4
SC*3
SC*3
41
42
43
95
45
46
TB15
TB5
TB02
TB5
LOSSNAY
TB5
TB5
TB5
TB15
BC controller
(Sub1)
Group 2
Group 1
Group 21
Group 32
Group 33
Group 31
Group 34
Group 35
TB3
TB7
TB7
TB7
TB7
TB7
TB3
TB2
000 or 201
203
202
Power supply unit
(PAC-SC51KUA)
52
51
OC
OS
PURY
SC*3
TB3
TB3
92
91
OC
OS
PURY
TB3
98
OC
CN41
CN40
CN41
CN40
CN41
CN40
CN41
CN40
CN41
CN40
ON
DipSW5-1
ON
DipSW5-1
ON
DipSW5-1
ON
DipSW5-1
ON
DipSW5-1
PURY
47
TB5
TM4
LOSSNAY
Group 36