4 - 87
2. M-NET control
YKB/YLM 2nd
S.D. R2
MEE15K022
2-4-3-2. MA remote controller, Single-refrigerant-system, System Controller
2. Address should be set to Indoor units and centralized controller.
3. For a system having more than 32 indoor unit (P15-P140), confirm the need of Booster at
2-3 "System configuration
    
restrictions".
NOTE:
1. Outdoor units OC and OS in one refrigerant circuit system are automatically detected.
    OC and OS are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order
    of their address.
Indoor unit
MA R/C
MA R/C
MA R/C
(Main)
(Sub)
MA R/C
SRU
Wireless R/C
1*
*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
*SC can be connected to TB3 side or TB7 side;
 Should SC connected to TB7 side, change Jumper from CN41 to CN40 at the Outdoor unit module so as to supply power to the SC.
1*
201
SC
01
02
03
04
05
TB15
TB5
TB5
TB5
TB5
TB5
TB15
TB15
TB15
TB15
TB02
53
BC controller
Group 2
Group 1
Group 3
Group 4
TB3
TB3
52
51
OC
OS
PURY
TB3
51
OC
CN41
CN40
CN41
CN40
CN41
CN40
ON
DipSW5-1
ON
DipSW5-1
ON
DipSW5-1
PURY
<Two outdoor units>
<One outdoor unit>
4. Indoor units should be set with a branch number.
5. When a PAR-31MAA(E) is connected to a group, no other MA remote controllers can be connected to the same group.