2. M-NET control
YKB/YLM 2nd
4 - 80
S.D. R2
MEE15K022
2-2. Transmission cable specifications
Type of cable
Cable size
Remarks
Sheathed 2-core cable (unshielded) CVV
Shielding wire (2-core)
CVVS, CPEVS or MVVS
Transmission cables (L
i
)
M-NET remote controller cables
CVVS, MVVS: PVC insulated PVC jacketed shielded control cable
CPEVS: PE insulated PVC jacketed shielded communication cable
CVV: PV insulated PVC sheathed control cable
*1 Connected with PZ-52SF.
*2 T
o wire PAR-31MAA(E), Simple MA remote controller use a wire with
a diameter of 0.3 mm
2
[AWG22]
*3 When a PAR-31MAA(E) and other MA remote controllers are connected in
the same group, the maximum length of cable should be 100 m.
MA Remote controller cables
When 10 m [32ft] is exceeded, use cables with
the same specification as transmission cables.
More than 1.25 mm
2
[AWG16]
0.3 1.25 mm [AWG22 16]
2
2
(0.75 1.25 mm [AWG18 16])
Max length: 200 m [656ft]
Max length: within 200 m
2
0.3 1.25 mm [AWG22 16]