3 - 104
Controller
MEE15K022
3. System remote controller
YKB/YLM 2nd
2. Wiring Instructions
(1). Connecting the Power and M-NET Transmission Lines
CAUTION
• Use a power line and M-NET transmission line that satisfy the specifications described in "1-(2). Parts
Purchased Separately".
• Attach a circuit comprising the following components to the supply primary side of the 24 VDC power supply
.
(1) Varistor, (2) Arrester, (3) Noise filter
, (4) Fuse
• It is important to pay attention to the polarity when connecting to the 24 VDC power supply terminal block.
Connecting the positive and negative in the reverse order will cause a failure.
• Fix the power line and M-NET transmission line in place on the outside to ensure that the terminal block is not
affected by any external force.
Not securely connecting and fixing the wires in place may cause heat generation and fire.
• Make sure that the copper wiring is not short-circuiting the plates (cover, lower case) or neighboring wires.
Cover the shielded line of the M-NET transmission line with materials such as vinyl tape and prevent
short-circuiting with the plates.
NOTE
• If the M-NET transmission line of this device is connected to an M-NET indoor control line and the outdoor
unit is down because, for example, the power supply is interrupted for servicing or there is a failure, the AI
controller cannot be set and monitored from the system controller.
• Be sure to ground this device, PAC-SC51KUA and 24 VDC Power source.
Measurement accuracy may be affected if devices are not grounded.
S
FG
M-NET
S / B /
A
(M1)
(M2)
U
U
R
V+/V-/FG
CN02
A/B/S
Tightening torque for terminal screws: 1 N
·
m
Connect the M-NET transmission line of this device to a power
supply unit (PAC-SC51KUA) for the M-NET transmission line
or an outdoor unit (either a centralized control line or indoor
control line can be connected).
* Only the M-NET circuitry of this device receives the power from the
M-NET transmission line. The power consumption factor is "1/4".
AI controller
Field
Connections
(example)
Fuse
V
a
ristor
Arrester
Noise
Filter
24 VDC
Power
source
AC power Line
*
Functional
ground
V
aristor