1 .. 767 768 769 770 771 772 773 774 775 776 777 .. 908
3 - 101
Controller
MEE15K022
3. System remote controller
YKB/YLM 2nd
1. Specifications
 
(1). Device Specifications
 
 
*1: Supply electric power from a power supply unit for the transmission line or an outdoor unit. Furthermore, the power consumption
 
factor of the M-NET circuitry of this unit is "1/4".
*2: Configure the dip switch settings for the analog input method to use.
*3: The measurement error for the system includes the measurement error for this unit, sensor, and wiring.
 
a%FS (full scale) = a% × ([measurement range's upper limit value] - [lower limit value])
*4: Settings for the interlock function are performed from the Maintenance Tool. For details, refer to the operation manual for the
 Maintenance Tool.
*5: M3 and M3.5 are sizes of the screw on the terminal block (ISO metric screw thread). The number indicates the screw diameter
   (mm).
 
 
Item
Description
Power
Supply
24 VDC   10%: 5 W
Screw terminal
block (M3) (*5)
Interface
M-NET communication
17 to 30 VDC (*1)
Screw terminal
block (M3) (*5)
Input
Ch
Sensor
Measurement
target
Measurement
range
Measurement error
External
connection method
Ch1
Pt100
(3-wire system)
Temperature
-30 to 60
[-22 to 140    ]
   0.3%FS    0.1    (0.18   )
(*3)
[at 25    (77   )]
Screwless terminal
block (3 poles)
Analog
4 to 20 mADC
Temperature/
humidity
(Set by system
controller)
   0.5%FS    0.1    (0.18   )
(*3)
   0.5%FS    0.1%RH
[at 25    (77   )]
Screwless terminal
block (2 poles)
1 to 5 VDC
0 to 10 VDC
Ch2
Analog
4 to 20 mADC
Temperature/
humidity
(Set by system
controller)
   0.5%FS    0.1    (0.18   )
(*3)
   0.5%FS    0.1%RH
[at 25    (77   )]
Screwless terminal
block (2 poles)
1 to 5 VDC
(*2)
0 to 10 VDC
Output
Upper/lower limit
alarm interlock output
(non-voltage contact)
Applied load
MAX: 24 VDC, 5 W
MIN: 5 VDC, 2 mW
* AC loads cannot be connected.
Screw terminal
block (M3.5) (*5)
Interlock
Function
Interlock M-NET devices according to measurement data values. (*4)
Environment
Conditions
Temperature
Operating temperature range
0 to 40     [32     to 104    ]
Storage temperature range
-20 to 60     [-4    to 140    ]
Humidity
30 to 90%RH (no condensation)
Dimensions
200 (W) × 120 (H) × 45 (D) mm / 7
7
/
8
 (W) × 4
3
/
4
 (H) × 1
25
/
32
 (D) in
Weight
0.6 kg / 1
3
/
8
 lb
Time Backup
During Power
Failure
In the event of power failure or shut-off, the internal capacitor will continue to track time for approximately one week.
(The internal capacitor takes about 24 hours to fully charge; a replacement battery is not necessary.)
Installation
Environment
Inside the metal control board (indoors)
* Use this product in a hotel, a business office environment or similar environment.