Controller
MEE15K022
3. System remote controller
YKB/YLM 2nd
3. Interlock control
 
The DIDO controller (P
AC-YG66DCA) has an interlock control function, which enables operation or set temperature change on the
M-NET devices such as indoor units and also enables signal output to the contacts on the DIDO controller.
Interlock control covers the units connected to the DIDO controller with M-NET system.
AE-200E/AE-50E/EW-50E/AG-150A/EB-50GU-J must be connected to use the function.
Ask your dealer for interlock control setting. The setting requires special tool support.
 
CAUTION
 
Before using the interlock control, you must agree to the following.
1.This feature must not be used for disaster prevention or security purpose.
(Not designed to be used in situations that are life-threatening)
2.No functions must be added that allow the malfunctioning unit to run by defeating the safety features, such as
an external ON/OFF switch or a short-circuit.
3.Those settings for the function that are not supported by the interlocked units must not be made. All the
settings must be made within the specified range.
(Failure to observe these precautions may result in malfunctions and failures.)
4.Perform a test run for interlock control, and confirm the correct settings and normal operation.
5.The system must be configured in the way that integrates the operation of the interlocked fire and emergency
control systems.
 
 
Number of events
24 events
1 event interlock with 1 unit
Item
Content
Remarks
Determinant condition for
interlock control
At input contact change
• Operation input ON/OFF
• Error input Error/Normal
Interlock control contents
(to be output)
1 action for 1 condition
• ON/OFF operation of indoor units
• Operation mode change of indoor units
• Temperature setting of indoor units
• Contact output to DIDO controller (*2)
(*1)
(*1) Temperature setting range: 19-28ºC (Standard setting)
Interlock control covers the units connected to
DIDO controllers with M-NET system.
 
(*2) DIDO controller itself or other DIDO controllers
in the same M-NET system.
Other
Interlock control prohibition function is
enabled at emergency stop from AE-200E/
AE-50E/EW-50E/AG-150A/EB-50GU-J
 
 
Interlock control of DIDO controller (example)
Note: Do not use Interlock control function on both AE-200E/AE-50E/EW-50E/AG-150A/EB-50GU-J and DIDO controller at the same time.
DIDO Controller
 
ON/OFF
Lights
ON/OFF
Indoor unit  
Operation ON/OFF
Outdoor unit
Interlock with contact output
Interlock with M-NET devices
AE-200E
(EW-50E)