Controller
MEE15K022
3. System remote controller
YKB/YLM 2nd
3-5. Centralized controller [AG-150A]
Operation mode
switching
T
emperature
setting
Sliding
T
emperature
setting
Night setback
setting
Fan speed setting
Models with 5 air flow speed settings: Hi/Mid-1/Mid-2/Low, Auto
Models with 4 air flow speed settings: Hi/Mid/Low, Auto
Models with 2 air flow speed settings: Hi/Low
Fan speed setting (including Auto) varies depending on the model.
Air flow direction
setting
Permit / Prohibit
local operation
Schedule
operation
This operates air conditioner units in test run mode.
Indoor unit intake
temperature
Measures the intake temperature of the indoor unit only when
the indoor unit is operating.
Error
T
est run
ON/OFF
ON and OFF operation for the air conditioner units
Ventilation
equipment
External
input/output
Item
Description
Operations
Display
Air flow direction angles, 4-angle or 5-angle Swing, Auto
 1: Louver cannot be set.
Air flow direction settings vary depending on the model.
:Each unit
:Collective
:Each block
:Each group
:Each floor
:Not available
1
2
3
4
6
6
Functions
A.
Microsoft
®
 Internet Explorer
®
 Ver. 6 or later by Microsoft Corporation is needed.
 (As of December 2012, operation with Internet Explorer
®
 Ver.6~9 are tested)
 (Note: You must have operating system which complies with "Oracle
®
 Java
TM
 
  Plug-in". When using Internet Explorer
®
 (64 bit), use Java
TM
 Plug-in (64bit).)
Microsoft
®
, Internet Explorer
®
 is a registered trade mark of Microsoft
Corporation US in the USA and other countries.
B.
Together with integrated centralized control software
TG-2000A, and/or PI, DIDO controller, many optional
functions like "Charging", "Peak-cut", "Energy saving",
"General equipment management", "Scheduling" etc,
can be carried out. Details, please refer to sections of
TG-2000A and/or PI, DIDO controller, PLC software.
C.
One AG-150A can control maximum 50 units (including
LOSSNAY). Up to 150 units (including LOSSNAY) can
be controlled from one AG-150A connected with three
expansion controllers.
The integrated centralized control software TG-2000A
can manage maximum 2000 units (including LOSSNAY).
For details, refer to TG-2000A page.
D.
E.
F.
 
Taking advantage of AG-150A's Web functions,
alarming E-mail containing address and error code can
be sent to appointed E-mail address upon any fault
happen at the air conditioner system.
This could release standby personnel and save operation cost.
AG-150A features a 9"-wide color LCD touch panel.
The settings for air conditioning units can be changed
by touching the corresponding icons on the display.
The interlock-control option enables interlocked operations of
air conditioning unit groups and the general equipment groups,
based on the changes of status in the ON/OFF
, Mode, or Error
signals.(Can be set from the Web browser only)
External dimension
Unit:mm[in.]
The centralized controller of AG-150A combines Web
function (optional), which enable the air conditioner
system management on a PC browser screen. *1
The management even carried out at a long distance
place via public telephone line or internet.
CENTRALIZED CONTROLLER  AG-150A
185 (7-5/16)
272 (10-3/4)
300 (11-13/16)
Back View
Switches between Cool / Dry / Auto / Fan / Heat. (Group of
LOSSNAY unit : automatic ventilation/ vent - heat interchange/
normal ventilation)
Operation modes vary depending on the air conditioner unit.
Auto mode is the City Multi R2 and WR2 series only.
Range of temperature setting
     
This function helps keep the indoor temperature in the
temperature range while the units are stopped and during the
time this function is effective.
This function shifts the preset temperature by the preset
increment to reduce the temperature difference between the
indoor and outdoor air temperatures during cooling operation.
The maximum shifting temperature (+1    , +2    , +3    , +4    )
can be set for each group.
Weekly schedule can be set for each group of air conditioning units.
Optimal startup setting is also available.
 2 By registering a license for AG-150A, weekly (5 types), annual, and current day
scheduling function become available.
The system follows either the current day, annual schedule, or weekly, which are
in the descending order of overriding priority.
Twenty-four events can be scheduled per day, including ON/OFF, Mode,
Temperature Setting, Operation Prohibition, Vane Direction, and Fan Speed.
Five types of weekly schedule (Summer/Winter) can be set.
Settable items depend on the functions that a given air conditioning unit supports.
Individually prohibit operation of each local remote control
function (ON/OFF, Change operation mode, Set temperature,
Reset filter).
 3: When the local remote controller inactivation command is
received from the master system controller,
"Disabled"appears in inverted display on the operation setting screen.
When an error is currently occurring on an air conditioner unit,
the afflicted unit and the error code are displayed.
 4: When an error occurs, the "ON/OFF" LED flashes. The
operation monitor screen shows the abnormal unit by flashing
it. The error monitor screen shows the abnormal unit address,
error code and source of detection. The error log monitor
screen shows the time and date, the abnormal unit address,
error code and source of detection.
The interlocked system settings can be performed by the master
system controller.
When setting the interlocked system, you can use the ventilation
switch to switch the free plan LOSSNAY settings between "Hi",
"Low" and "Stop".
When setting a group of only free plan LOSSNAY units, you can
switch between "Normal ventilation", "Interchange ventilation"
and "Automatic ventilation".
By using accessory cables you can set and monitor the following.
   Input: By level signal: "Batch ON/OFF", "Batch emergency stop"
             By pulse signal: "Batch ON/OFF", "Enable/disable local remote
             controller"
   Output: "ON/OFF", "Error/Normal"
6: Requires an external I/O cable (PAC-YG10HA-E; sold separately) and a
commercially available external power supply.
 Range of temperature settings vary depending on model.
Cool/Dry
:
Heat
 
:
Auto
 
:
Note:
Connect AG-150A to a private network.
 
Use a security device such as a VPN router when
 
connecting the AG-150A to the Internet to prevent
unauthorized
access.
5
250 (9-7/8)
272 (10-3/4)
146 (5-3/4)
167 (6-5/8)
8 (3/8)
4.5(3/16)
44.7 (1-
13
/16)
25.6 (1-1/16)
NOTE: Depending on the versions of AG-150A, some of the functions may not be available.
The external input/output terminal on AG-150A becomes unavailable when AG-150A is
connected to PAC-YG50ECA. Use the terminals on PAC-YG50ECA in that case.
*AG-150A connected with PAC-YG50ECA cannot be connected to the
PLC (PAC-YG21CDA).
*5 When setting ventilation interlock with Mr.Slim units, the air conditioning
    and interlocked ventilation icon will display ON even when the interlocked
    LOSSNAY is operating by itself.
   (This will occur when used with the following M-NET adapter:
    PAC-SF48/50/60/70/80/81MA-E)
Oracle® and Java
TM
 are trademarks or registered trademarks of
Oracle Corporation in the United States and/or other countries.
290.8 (11-1/2)
A type installation plate
B type installation plate
273 (10-3/4)
250 (9-7/8)
200 (7-7/8)
147 (5-13/16)
6
(1/4)
4
(3/16)
163.4 (6-7/16)
167 (6-5/8)
175.8 (6-15/16)
300 (11-13/11)
278 (10-15/16)
250 (9-7/8)
200 (7-7/8)
6
(1/4)
4
(3/16)
152 (6)
163.4 (6-7/16)
167 (6-5/8)
185 (7-5/16)