3 - 38
Controller
MEE15K022
3. System remote controller
YKB/YLM 2nd
(4) Recommended circuit
(A) Level signal
CN5
X1
X2
Y1
Y2
9
8
7
6
5
1
X1
X2
Y1
Y2
Use relays X1, X2, Y1, and Y2 that meet the
following specifications.
Contact rating
Rated voltage: 12 VDC or above
Rated current: 0.1 A or above
Minimum applied load: DC 1 mA
Important
●
Be sure to use an external power supply (12
or 24 VDC) to avoid malfunctions.
●
Connect the external power supply in the
correct polarity to avoid malfunctions.
(B) Pulse signal
CN5
X1
X2
Y1
Y2
X1
X2
Y1
Y2
9
8
7
6
5
1
Note
●
The relays, external power supply, and extension cables are not supplied.
●
The total length of the lead wire and extension cable should not exceed 10 m (32 ft). (Use an extension cable of 0.3 mm
2
or
thicker.)
●
Cut the excess cable near the connector, and insulate the end of the unused cable with tape.
ON/OFF or Emergency
stop
Demand level 1
Red
Orange
Max.
10 m (32 ft)
AE-200/AE-50
Yellow
Blue
Gray
External power supply *1 (12 or 24 VDC)
Demand level 2
Demand level 3
Demand level 4
Permit
Prohibit
OFF
ON
External power supply *1 (12 or 24 VDC)
Red
Gray
Blue
Yellow
Orange
Max.
10 m (32 ft)
AE-200/AE-50
*1
Select an external power supply suitable for the
relays used. (12 or 24 VDC)
Connect the external power supply in the correct
polarity to input and output the signals.
Connect
–
(see the figure at left) to the negative
side.
5
8