Controller
MEE15K022
3. System remote controller
YKB/YLM 2nd
(4) Recommended circuit
(A) Level signal
CN5
X1
X2
Y1
Y2
9
8
7
6
5
1
X1
X2
Y1
Y2
Use relays X1, X2, Y1, and Y2 that meet the
following specifications.
Contact rating
 
Rated voltage: 12 VDC or above
 
Rated current: 0.1 A or above
 
Minimum applied load: DC 1 mA
 
 
Important
 
Be sure to use an external power supply (12
or 24 VDC) to avoid malfunctions.
 
Connect the external power supply in the
correct polarity to avoid malfunctions.
(B) Pulse signal
CN5
X1
X2
Y1
Y2
X1
X2
Y1
Y2
9
8
7
6
5
1
Note
 
The relays, external power supply, and extension cables are not supplied.
 
The total length of the lead wire and extension cable should not exceed 10 m (32 ft). (Use an extension cable of 0.3 mm
2
 or
thicker.)
 
Cut the excess cable near the connector, and insulate the end of the unused cable with tape.
ON/OFF or Emergency
stop
Demand level 1
Red
Orange
Max.
10 m (32 ft)
AE-200/AE-50
Yellow
Blue
Gray
External power supply *1 (12 or 24 VDC)
Demand level 2
Demand level 3
Demand level 4
Permit
Prohibit
OFF
ON
External power supply *1 (12 or 24 VDC)
Red
Gray
Blue
Yellow
Orange
Max.  
10 m (32 ft)
AE-200/AE-50
*1
Select an external power supply suitable for the
relays used. (12 or 24 VDC)
Connect the external power supply in the correct
polarity to input and output the signals.
Connect
 (see the figure at left) to the negative
side.