3 - 35
Controller
MEE15K022
3. System remote controller
YKB/YLM 2nd
Centralized controller
EW-50E
M-NET
ME remote
controller
M-NET
M-NET
ME remote
controller
ME remote
controller
1. Power supply to EW-50E
EW-50E needs AC power (100-240VAC) and M-NET
; the former is for centralized control transmission use and the latter is
for EW-50E's operating and LAN function use.
Except when the power consumption coefficient exceeds 1.5, the power supply unit, the power supply unit PAC-SC51KUA
or the power supply from the outdoor unit to M-NET is not necessary.
For more details, please refer to the Installation Manual of EW-50E.
 
(1). The basic scheme is as follows.
Fig.1 EW-50E basic scheme.  
2. M-NET power supply
Supplying power from the outdoor unit or the power supply unit, it is necessary to disconnect the M-NET
power jumper CN21. (At factory setting, CN21 is connected.)
When the power consumption coefficient exceeds 1.5, it is necessary to connect the power supply unit
(PAC-SC51KUA), and disconnect the M-NET power jumper CN21 on EW-50E.
Note
When connecting both EW-50E and BAC-HD150 (BM ADAPTER) to the same M-NET system,
certain restrictions apply. Consult your dealer for details.
LOSSNAY
remote
controller
LOSSNAY unit
M-NET remote controller
ON/OFF remote
controller
Advanced touch
controller
ME remote Controller
LOSSNAY remote
controller
0.25
1
 
Power consumption coefficient
6 units
0.5
3 units
1 unit
1.5
1 unit
Connectable units
System controller
EW-50E has a built-in function to supply power to the M-NET transmission line. (power supply coefficient:1.5)
When power is supplied from EW-50E, the types of system controllers listed in the table below are connectable.