3 - 27
Controller
MEE15K022
3. System remote controller
YKB/YLM 2nd
[External signal output function]
An ON signal is output when one or more units are in operation, and an Error signal is output when one or more units are
in error.
(1) External signal output specifications
CN5
Lead wire from
P
AC-YG10HA-E
Signal
No. 1
Green
Common ground for external output (Ground for the external power supply)
No. 2
Black
ON signal*, OFF signal
No. 3
Brown
Error signal, Normal signal
*
The operation status of general equipment (via a DIDO controller (PAC-YG66DCA)) will not be output.
*
The ON signal will be output even during an error.
(2) Recommended circuit
Relay-driven circuit
CN5
4
9
3
2
1
Z1
L1
Z2
L2
Z1
Z2
Use relays Z1 and Z2 that meet the following
specifications.
Operation coil
Rated voltage: 12 or 24 VDC
Power consumption: Max. 0.9 W
Important
●
Be sure to use an external power supply (12 or 24 VDC)
to avoid malfunctions.
●
Connect the external power supply in the correct
polarity to avoid malfunctions.
●
Do not connect the external power supply without
relays being connected to the controller (no load).
Note
●
The relays, lamps, external power supply, diodes, and extension cables are not supplied.
●
The total length of the lead wire and extension cable should not exceed 10 m (32 ft). (Use an extension cable of 0.3 mm
2
or
thicker.)
●
Each element will turn on during operation and when an error occurs.
Green
Max.
10 m (32 ft)
Black
Brown
External power supply *1
Diode *2
L1: ON indicator
L2: Error indicator
AE-200/AE-50
*1
Select an external power supply suitable for the relays used. (12 or
24 VDC)
Connect the external power supply in the correct polarity to input
and output the signals.
*2
Use a diode at both ends of the relay coils.
Connect
(shown in the figure at left) to the negative side.
1
Punch out the knockout hole
Note
* When connecting the external input/output cables to connector CN5
on the controller, punch out the knockout hole.