1 .. 50 51 52 53 54 55 56 57 58 59 60 .. 908
1. SPECIFICATIONS
YKB/YLM 2nd
1 - 50
PEFY-
VM
A(
L),
 VMA3
MEE15K022
 Model
PEFY-P100VMA-E
PEFY-P125VMA-E
PEFY-P140VMA-E
PEFY-P20VMA3-E
 Power source
1-phase 220-230-240V
50/60Hz
1-phase 220-230-240V
50/60Hz
1-phase 220-230-240V
50/60Hz
1-phase 220-230-240V
50/60Hz
 Cooling capacity
*1
kW
11.2
14.0
16.0
2.2
(Nominal)
*1
kcal / h
9,600
12,000
13,800
1,900
*1
BTU / h
38,200
47,800
54,600
7,500
*2
Power input
kW
0.24
0.34
0.36
0.110
*2
Current input
A
1.47
2.05
2.21
0.90
 Heating capacity
*3
kW
12.5
16.0
18.0
2.5
(Nominal)
*3
kcal / h
10,800
13,800
15,500
2,200
*3
BTU / h
42,700
54,600
61,400
8,500
*2
Power input
kW
0.22
0.32
0.34
0.090
*2
Current input
A
1.36
1.94
2.10
0.79
External finish
Galvanized steel plate
Galvanized steel plate
Galvanized steel plate
Galvanized steel plate
External dimension HxWxD
mm
250 x 1,400 x 732
250 x 1,400 x 732
250 x 1,600 x 732
250 x 900 x 732
inch
9-7/8 x 55-1/8 x 28-7/8
9-7/8 x 55-1/8 x 28-7/8
9-7/8 x 63 x 28-7/8
9-7/8 x 35-7/16 x 28-7/8
 Net weight
kg(lbs)
42(93)
42(93)
46(102)
27(60)
 Heat exchanger
Cross fin(Aluminum fin and
copper tube)
Cross fin(Aluminum fin and
copper tube)
Cross fin(Aluminum fin and
copper tube)
Cross fin(Aluminum fin and
copper tube)
FAN
Type x Quantity
Sirocco fan x 2
Sirocco fan x 2
Sirocco fan x 2
Sirocco fan x 1
*4
External static press.
Pa
<35> - 50 - <70> - <100> -
<150>
<35> - 50 - <70> - <100> -
<150>
<35> - 50 - <70> - <100> -
<150>
<35> - 50 - <70> - <100> -
<125>
mmH
2
O
<3.6> - 5.1 - <7.1> - <10.2> -
<15.3>
<3.6> - 5.1 - <7.1> - <10.2> -
<15.3>
<3.6> - 5.1 - <7.1> - <10.2> -
<15.3>
<3.6> - 5.1 - <7.1> - <10.2> -
<12.7>
Motor Type
DC motor
DC motor
DC motor
DC motor
Motor output
kW
0.244
0.244
0.244
0.085
Driving mechanism
Direct-driven by motor°
Direct-driven by motor
Direct-driven by motor
Direct-driven by motor
Air flow rate
(Low-Mid-High)
(Low-Mid-High)
(Low-Mid-High)
(Low-Mid-High)
m
3
 / min
23.0 - 28.0 - 33.0
28.0 - 34.0 - 40.0
29.5 - 35.5 - 42.0
12.0 - 14.5 - 17.0
L/s
383 - 467 - 550
467 - 567 - 667
492 - 592 - 700
200 - 242 - 283
cfm
812 - 989 - 1,165
989 - 1,201 - 1,412
1,042 - 1,254 - 1,483
424 - 512 - 600
 Sound pressure level (measured in anechoic room)
(Low-Mid-High)
(Low-Mid-High)
(Low-Mid-High)
(Low-Mid-High)
*2 *5
dB <A>
32-37-41
35-40-44
36-41-45
30-35-39
*2 *6
dB <A>
28-33-37
32-36-40
33-37-42
26-34-35
 Insulation material
EPS, Polyethylene foam,
Urethane foam
EPS, Polyethylene foam,
Urethane foam
EPS, Polyethylene foam,
Urethane foam
EPS, Polyethylene foam,
Urethane foam
Air filter
PP honeycomb fabric.
PP honeycomb fabric.
PP honeycomb fabric.
PP honeycomb fabric.
 Protection device
Fuse
Fuse
Fuse
Fuse
 Refrigerant control device
LEV
LEV
LEV
LEV
Connectable outdoor unit
R410A CITY MULTI
R410A CITY MULTI
R410A CITY MULTI
R410A CITY MULTI
 Diameter of refrigerant
Liquid (R410A)
mm(in.
)
9.52(3/8)Brazed
9.52(3/8)Brazed
9.52(3/8)Brazed
6.35 (1/4)Flare
 pipe
Gas (R410A)
mm(in.)
15.88(5/8)Brazed
15.88(5/8)Brazed
15.88(5/8)Brazed
12.7 (1/2)Flare
Field drain pipe size
mm(in.
)
O.
D.
32(1-1/4)
O.
D.
32(1-1/4)
O.
D.
32(1-1/4)
O.
D.
32(1-1/4)
 Drawing
External
IU-KB94-R528
IU-KB94-R528
IU-KB94-R528
IU-KJ94-T342
Wiring
IU-KB94-R069
IU-KB94-R069
IU-KB94-R069
IU-KJ94-T343
Refrigerant cycle
-
-
-
-
 Standard attachment
Document
Installation Manual, Instruc-
tion Book
Installation Manual, Instruc-
tion Book
Installation Manual, Instruc-
tion Book
Installation Manual, Instruc-
tion Book
Accessory
Insulation pipe for refrigerant
pipe, Washer, Drain hose,
Tie band
Insulation pipe for refrigerant
pipe, Washer, Drain hose,
Tie band
Insulation pipe for refrigerant
pipe, Washer, Drain hose,
Tie band
Insulation pipe for refrigerant
pipe, Washer, Drain hose,
Tie band
 Optional parts
Filter box
PAC-KE94TB-E
PAC-KE94TB-E
PAC-KE95TB-E
PAC-KE92TB-E
Remarks
* Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be
referred to the Installation Manual.
* Due to continuing improvement, above specifications may be subject to change without notice.
Notes:
Unit converter
 1.Nominal cooling conditions
Indoor:27°CDB/19°CWB(81°FDB/66°FWB), Outdoor:35°CDB(95°FDB)
Pipe length:7.5m(24-9/16ft.
), Level difference:0m(0ft.)
 kcal/h
 BTU/h
 cfm
=kW x 860
=kW x 3,412
=m
3
/min x 35.31
2.The values are measured at the factory setting of external static pressure.
 lbs
=kg / 0.4536
3.Nominal heating conditions
Indoor:20°CDB(68°FDB), Outdoor:7°CDB/6°CWB(45°FDB/43°FWB)
Pipe length:7.5m(24-9/16ft.
), Level difference:0m(0ft.)
4.The factory setting of external static pressure is shown without < >.
Refer to "Fan characteristics curves", according to the external static pressure, in DATA BOOK for the usable range of air flow rate.
5.Measured in anechoic room with a 1m air inlet duct and 2m air outlet duct attached to the unit and 1.5m below the unit. Refer to 5-1-1 for details.
 *Above specification data is
6.Measured in anechoic room with a 2m air inlet duct and 2m air outlet duct attached to the unit and 1.5m below the unit. Refer to 5-1-2 for details.
 subject to rounding variation.