1. SPECIFICATIONS
YKB/YLM 2nd
1 - 48
PEFY-
VM
A(
L),
 VMA3
MEE15K022
I.
Ceiling concealed (Middle static pressure type)
1. SPECIFICATIONS
 Model
PEFY-P20VMA-E
PEFY-P25VMA-E
PEFY-P32VMA-E
PEFY-P40VMA-E
 Power source
1-phase 220-230-240V
50/60Hz
1-phase 220-230-240V
50/60Hz
1-phase 220-230-240V
50/60Hz
1-phase 220-230-240V
50/60Hz
 Cooling capacity
*1
kW
2.2
2.8
3.6
4.5
(Nominal)
*1
kcal / h
1,900
2,400
3,100
3,900
*1
BTU / h
7,500
9,600
12,300
15,400
*2
Power input
kW
0.06
0.06
0.07
0.09
*2
Current input
A
0.53
0.53
0.55
0.64
 Heating capacity
*3
kW
2.5
3.2
4.0
5.0
(Nominal)
*3
kcal / h
2,200
2,800
3,400
4,300
*3
BTU / h
8,500
10,900
13,600
17,100
*2
Power input
kW
0.04
0.04
0.05
0.07
*2
Current input
A
0.42
0.42
0.44
0.53
External finish
Galvanized steel plate
Galvanized steel plate
Galvanized steel plate
Galvanized steel plate
External dimension HxWxD
mm
250 x 700 x 732
250 x 700 x 732
250 x 700 x 732
250 x 900 x 732
inch
9-7/8 x 27-9/16 x 28-7/8
9-7/8 x 27-9/16 x 28-7/8
9-7/8 x 27-9/16 x 28-7/8
9-7/8 x 35-7/16 x 28-7/8
 Net weight
kg(lbs)
23(51)
23(51)
23(51)
26(58)
 Heat exchanger
Cross fin(Aluminum fin and
copper tube)
Cross fin(Aluminum fin and
copper tube)
Cross fin(Aluminum fin and
copper tube)
Cross fin(Aluminum fin and
copper tube)
FAN
Type x Quantity
Sirocco fan x 1
Sirocco fan x 1
Sirocco fan x 1
Sirocco fan x 1
*4
External static press.
Pa
<35> - 50 - <70> - <100> -
<150>
<35> - 50 - <70> - <100> -
<150>
<35> - 50 - <70> - <100> -
<150>
<35> - 50 - <70> - <100> -
<150>
mmH
2
O
<3.6> - 5.1 - <7.1> - <10.2> -
<15.3>
<3.6> - 5.1 - <7.1> - <10.2> -
<15.3>
<3.6> - 5.1 - <7.1> - <10.2> -
<15.3>
<3.6> - 5.1 - <7.1> - <10.2> -
<15.3>
Motor Type
DC motor
DC motor
DC motor
DC motor
Motor output
kW
0.085
0.085
0.085
0.085
Driving mechanism
Direct-driven by motor
Direct-driven by motor
Direct-driven by motor
Direct-driven by motor
Air flow rate
(Low-Mid-High)
(Low-Mid-High)
(Low-Mid-High)
(Low-Mid-High)
m
3
 / min
6.0 - 7.5 - 8.5
6.0 - 7.5 - 8.5
7.5 - 9.0 - 10.5
10.0 - 12.0 - 14.0
L/s
100 - 125 - 142
100 - 125 - 142
125 - 150 - 175
167 - 200 - 233
cfm
212 - 265 - 300
212 - 265 - 300
265 - 318 - 371
353 - 424 - 494
 Sound pressure level (measured in anechoic room)
(Low-Mid-High)
(Low-Mid-High)
(Low-Mid-High)
(Low-Mid-High)
*2 *5
dB <A>
26-28-29
26-28-29
28-30-34
28-30-34
*2 *6
dB <A>
23-25-26
23-25-26
23-26-29
23-27-30
 Insulation material
EPS, Polyethylene foam,
Urethane foam
EPS, Polyethylene foam,
Urethane foam
EPS, Polyethylene foam,
Urethane foam
EPS, Polyethylene foam,
Urethane foam
Air filter
PP honeycomb fabric.
PP honeycomb fabric.
PP honeycomb fabric.
PP honeycomb fabric.
 Protection device
Fuse
Fuse
Fuse
Fuse
 Refrigerant control device
LEV
LEV
LEV
LEV
Connectable outdoor unit
R410A CITY MULTI
R410A CITY MULTI
R410A CITY MULTI
R410A CITY MULTI
Diameter of refrigerant
Liquid (R410A)
mm(in.
)
6.35(1/4)Brazed
6.35(1/4)Brazed
6.35(1/4)Brazed
6.35(1/4)Brazed
 pipe
Gas (R410A)
mm(in.
)
12.7(1/2)Brazed
12.7(1/2)Brazed
12.7(1/2)Brazed
12.7(1/2)Brazed
Field drain pipe size
mm(in.
)
O.
D.
32(1-1/4)
O.
D.
32(1-1/4)
O.
D.
32(1-1/4)
O.
D.
32(1-1/4)
 Drawing
External
IU-KB94-R528
IU-KB94-R528
IU-KB94-R528
IU-KB94-R528
Wiring
IU-KB94-R069
IU-KB94-R069
IU-KB94-R069
IU-KB94-R069
Refrigerant cycle
-
-
-
-
 Standard attachment
Document
Installation Manual, Instruc-
tion Book
Installation Manual, Instruc-
tion Book
Installation Manual, Instruc-
tion Book
Installation Manual, Instruc-
tion Book
Accessory
Insulation pipe for refrigerant
pipe, Washer, Drain hose,
Tie band
Insulation pipe for refrigerant
pipe, Washer, Drain hose,
Tie band
Insulation pipe for refrigerant
pipe, Washer, Drain hose,
Tie band
Insulation pipe for refrigerant
pipe, Washer, Drain hose,
Tie band
 Optional parts
Filter box
PAC-KE91TB-E
PAC-KE91TB-E
PAC-KE91TB-E
PAC-KE92TB-E
Remarks
* Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be
referred to the Installation Manual.
* Due to continuing improvement, above specifications may be subject to change without notice.
Notes:
Unit converter
 1.Nominal cooling conditions
Indoor:27°CDB/19°CWB(81°FDB/66°FWB), Outdoor:35°CDB(95°FDB)
Pipe length:7.5m(24-9/16ft.
), Level difference:0m(0ft.)
 kcal/h
 BTU/h
 cfm
=kW x 860
=kW x 3,412
=m
3
/min x 35.31
2.The values are measured at the factory setting of external static pressure.
 lbs
=kg / 0.4536
3.Nominal heating conditions
Indoor:20°CDB(68°FDB), Outdoor:7°CDB/6°CWB(45°FDB/43°FWB)
Pipe length:7.5m(24-9/16ft.
), Level difference:0m(0ft.)
4.The factory setting of external static pressure is shown without < >.
Refer to "Fan characteristics curves", according to the external static pressure, in DATA BOOK for the usable range of air flow rate.
5.Measured in anechoic room with a 1m air inlet duct and 2m air outlet duct attached to the unit and 1.5m below the unit. Refer to 5-1-1 for details.
 *Above specification data is
6.Measured in anechoic room with a 2m air inlet duct and 2m air outlet duct attached to the unit and 1.5m below the unit. Refer to 5-1-2 for details.
 subject to rounding variation.