1 .. 49 50 51 52 53 54 55 56 57 58 59 .. 908
1 - 49
1. SPECIFICATIONS
YKB/YLM 2nd
PEFY-VMA(L)
, VMA3
MEE15K022
 Model
PEFY-P50VMA-E
PEFY-P63VMA-E
PEFY-P71VMA-E
PEFY-P80VMA-E
 Power source
1-phase 220-230-240V
50/60Hz
1-phase 220-230-240V
50/60Hz
1-phase 220-230-240V
50/60Hz
1-phase 220-230-240V
50/60Hz
 Cooling capacity
*1
kW
5.6
7.1
8.0
9.0
 (Nominal)
*1
kcal / h
4,800
6,100
6,900
7,700
*1
BTU / h
19,100
24,200
27,300
30,700
*2
Power input
kW
0.11
0.12
0.14
0.14
*2
Current input
A
0.74
1.01
1.15
1.15
 Heating capacity
*3
kW
6.3
8.0
9.0
10.0
 (Nominal)
*3
kcal / h
5,400
6,900
7,700
8,600
*3
BTU / h
21,500
27,300
30,700
34,100
*2
Power input
kW
0.09
0.10
0.12
0.12
*2
Current input
A
0.63
0.90
1.04
1.04
 External finish
Galvanized steel plate
Galvanized steel plate
Galvanized steel plate
Galvanized steel plate
 External dimension HxWxD
mm
250 x 900 x 732
250 x 1,100 x 732
250 x 1,100 x 732
250 x 1,100 x 732
inch
9-7/8 x 35-7/16 x 28-7/8
9-7/8 x 43-5/16 x 28-7/8
9-7/8 x 43-5/16 x 28-7/8
9-7/8 x 43-5/16 x 28-7/8
 Net weight
kg(lbs)
26(58)
32(71)
32(71)
32(71)
 Heat exchanger
Cross fin(Aluminum fin and
copper tube)
Cross fin(Aluminum fin and
copper tube)
Cross fin(Aluminum fin and
copper tube)
Cross fin(Aluminum fin and
copper tube)
 FAN
Type x Quantity
Sirocco fan x 1
Sirocco fan x 2
Sirocco fan x 2
Sirocco fan x 2
*4
External static press.
Pa
<35> - 50 - <70> - <100> -
<150>
<35> - 50 - <70> - <100> -
<150>
<35> - 50 - <70> - <100> -
<150>
<35> - 50 - <70> - <100> -
<150>
mmH
2
O
<3.6> - 5.1 - <7.1> - <10.2> -
<15.3>
<3.6> - 5.1 - <7.1> - <10.2> -
<15.3>
<3.6> - 5.1 - <7.1> - <10.2> -
<15.3>
<3.6> - 5.1 - <7.1> - <10.2> -
<15.3>
Motor Type
DC motor
DC motor
DC motor
DC motor
Motor output
 kW
0.085
0.121
0.121
0.121
Driving mechanism
Direct-driven by motor
Direct-driven by motor
Direct-driven by motor
Direct-driven by motor
Air flow rate
(Low-Mid-High)
(Low-Mid-High)
(Low-Mid-High)
(Low-Mid-High)
m
3
 / min
12.0 - 14.5 - 17.0
13.5 - 16.0 - 19.0
14.5 - 18.0 - 21.0
14.5 - 18.0 - 21.0
L/s
200 - 242 - 283
225 - 267 - 317
242 - 300 - 350
242 - 300 - 350
cfm
424 - 512 - 600
477 - 565 - 671
512 - 636 - 742
512 - 636 - 742
 Sound pressure level (measured in anechoic room)
(Low-Mid-High)
(Low-Mid-High)
(Low-Mid-High)
(Low-Mid-High)
*2 *5
dB <A>
28-32-35
29-32-36
30-34-38
30-34-38
*2 *6
dB <A>
25-29-32
25-29-33
26-29-34
26-29-34
 Insulation material
EPS, Polyethylene foam,
Urethane foam
EPS, Polyethylene foam,
Urethane foam
EPS, Polyethylene foam,
Urethane foam
EPS, Polyethylene foam,
Urethane foam
 Air filter
PP honeycomb fabric.
PP honeycomb fabric.
PP honeycomb fabric.
PP honeycomb fabric.
 Protection device
Fuse
Fuse
Fuse
Fuse
 Refrigerant control device
LEV
LEV
LEV
LEV
 Connectable outdoor unit
R410A CITY MULTI
R410A CITY MULTI
R410A CITY MULTI
R410A CITY MULTI
 Diameter of refrigerant
Liquid (R410A)
mm(in.)
6.35(1/4)Brazed
9.52(3/8)Brazed
9.52(3/8)Brazed
9.52(3/8)Brazed
 pipe
Gas (R410A)
mm(in.)
12.7(1/2)Brazed
15.88(5/8)Brazed
15.88(5/8)Brazed
15.88(5/8)Brazed
 Field drain pipe size
mm(in.
)
O.
D.
32(1-1/4)
O.D.32(1-1/4)
O.D.32(1-1/4)
O.
D.
32(1-1/4)
 Drawing
External
IU-KB94-R528
IU-KB94-R528
IU-KB94-R528
IU-KB94-R528
Wiring
IU-KB94-R069
IU-KB94-R069
IU-KB94-R069
IU-KB94-R069
Refrigerant cycle
-
-
-
-
 Standard attachment
Document
Installation Manual, Instruc-
tion Book
Installation Manual, Instruc-
tion Book
Installation Manual, Instruc-
tion Book
Installation Manual, Instruc-
tion Book
Accessory
Insulation pipe for refrigerant
pipe, Washer, Drain hose,
Tie band
Insulation pipe for refrigerant
pipe, Washer, Drain hose,
Tie band
Insulation pipe for refrigerant
pipe, Washer, Drain hose,
Tie band
Insulation pipe for refrigerant
pipe, Washer, Drain hose,
Tie band
 Optional parts
Filter box
PAC-KE92TB-E
PAC-KE93TB-E
PAC-KE93TB-E
PAC-KE93TB-E
 Remarks
* Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be
referred to the Installation Manual.
* Due to continuing improvement, above specifications may be subject to change without notice.
Notes:
Unit converter
 1.Nominal cooling conditions
Indoor:27°CDB/19°CWB(81°FDB/66°FWB), Outdoor:35°CDB(95°FDB)
Pipe length:7.5m(24-9/16ft.), Level difference:0m(0ft.)
 kcal/h
 BTU/h
 cfm
=kW x 860
=kW x 3,412
=m
3
/min x 35.31
 2.The values are measured at the factory setting of external static pressure.
 lbs
=kg / 0.4536
 3.Nominal heating conditions
Indoor:20°CDB(68°FDB), Outdoor:7°CDB/6°CWB(45°FDB/43°FWB)
Pipe length:7.5m(24-9/16ft.), Level difference:0m(0ft.)
 4.The factory setting of external static pressure is shown without < >.
Refer to "Fan characteristics curves", according to the external static pressure, in DATA BOOK for the usable range of air flow rate.
 5.Measured in anechoic room with a 1m air inlet duct and 2m air outlet duct attached to the unit and 1.5m below the unit. Refer to 5-1-1 for details.
 *Above specification data is
 6.Measured in anechoic room with a 2m air inlet duct and 2m air outlet duct attached to the unit and 1.5m below the unit. Refer to 5-1-2 for details.
 subject to rounding variation.