1 - 282
CT
MEE15K022
6. Cooling [Ceiling suspended]
YKB/YLM 2nd
6-6. Cooling capacity with PUHY-P850-1350YSKB-A1, EP850-1350YSLM-A1
6-7. Cooling capacity with PURY-(E)P200-250YLM-A1
6-8. Cooling capacity with PURY-(E)P300-400Y(S)LM-A1
6-9. Cooling capacity with PURY-(E)P450-650Y(S)LM-A1
6-10. Cooling capacity with PURY-(E)P700-800YSLM-A1
PCFY-P-VKM-E
CA: Capacity (kW), SHC: Sensible Heat Capacity (kW)
Model size (Rated kW)
Indoor air temp.
21.5°C D.B.
23°C D.
B.
25°C D.
B.
27°C D.
B.
28°C D.
B.
30°C D.B.
32°C D.B.
15°C W.
B.
16°C W.B.
18°C W.B.
19°C W.B.
20°C W.B.
22°C W.B.
24°C W.B.
CA
SHC
CA
SHC
CA
SHC
CA
SHC
CA
SHC
CA
SHC
CA
SHC
40 (4.5)
4.0
2.9
4.1
3.0
4.4
3.0
4.5
3.2
4.7
3.2
5.0
3.1
5.4
3.1
63 (7.1)
6.3
4.6
6.5
4.7
6.9
4.7
7.1
4.9
7.4
4.9
7.9
4.9
8.5
4.8
100 (11.2)
10.0
7.1
10.2
7.2
11.0
7.2
11.2
7.5
11.7
7.6
12.5
7.5
13.4
7.4
125 (14.0)
12.5
8.8
12.8
9.0
13.7
9.0
14.0
9.4
14.7
9.4
15.7
9.3
16.7
9.2
* The capacity does not depend on the outdoor temperature.
kcal/h = kW x 860, BTU/h = kW x 3,412
PCFY-P-VKM-E
CA: Capacity (kW), SHC: Sensible Heat Capacity (kW)
Model size (Rated kW)
Indoor air temp.
21.5°C D.B.
23°C D.
B.
25°C D.
B.
27°C D.
B.
28°C D.
B.
30°C D.B.
32°C D.B.
15°C W.
B.
16°C W.B.
18°C W.B.
19°C W.B.
20°C W.B.
22°C W.B.
24°C W.B.
CA
SHC
CA
SHC
CA
SHC
CA
SHC
CA
SHC
CA
SHC
CA
SHC
40 (4.5)
4.1
3.0
4.2
3.0
4.4
3.0
4.5
3.2
4.7
3.2
4.9
3.1
5.2
3.1
63 (7.1)
6.4
4.6
6.6
4.7
7.0
4.7
7.1
4.9
7.4
4.9
7.8
4.8
8.2
4.7
100 (11.2)
10.1
7.1
10.4
7.3
11.0
7.2
11.2
7.5
11.6
7.5
12.2
7.4
13.0
7.3
125 (14.0)
12.6
8.9
13.0
9.1
13.8
9.0
14.0
9.4
14.5
9.4
15.3
9.2
16.2
9.1
* The capacity does not depend on the outdoor temperature.
kcal/h = kW x 860, BTU/h = kW x 3,412
PCFY-P-VKM-E
CA: Capacity (kW), SHC: Sensible Heat Capacity (kW)
Model size (Rated kW)
Indoor air temp.
21.5°C D.B.
23°C D.
B.
25°C D.
B.
27°C D.
B.
28°C D.
B.
30°C D.B.
32°C D.B.
15°C W.
B.
16°C W.B.
18°C W.B.
19°C W.B.
20°C W.B.
22°C W.B.
24°C W.B.
CA
SHC
CA
SHC
CA
SHC
CA
SHC
CA
SHC
CA
SHC
CA
SHC
40 (4.5)
4.1
3.0
4.1
3.0
4.4
3.0
4.5
3.2
4.7
3.2
5.0
3.1
5.3
3.1
63 (7.1)
6.4
4.6
6.5
4.7
6.9
4.7
7.1
4.9
7.4
4.9
7.9
4.8
8.4
4.8
100 (11.2)
10.1
7.1
10.3
7.3
11.0
7.2
11.2
7.5
11.7
7.6
12.4
7.5
13.2
7.4
125 (14.0)
12.6
8.9
12.8
9.0
13.7
9.0
14.0
9.4
14.6
9.4
15.5
9.3
16.5
9.2
* The capacity does not depend on the outdoor temperature.
kcal/h = kW x 860, BTU/h = kW x 3,412
PCFY-P-VKM-E
CA: Capacity (kW), SHC: Sensible Heat Capacity (kW)
Model size (Rated kW)
Indoor air temp.
21.5°C D.B.
23°C D.
B.
25°C D.
B.
27°C D.
B.
28°C D.
B.
30°C D.B.
32°C D.B.
15°C W.
B.
16°C W.B.
18°C W.B.
19°C W.B.
20°C W.B.
22°C W.B.
24°C W.B.
CA
SHC
CA
SHC
CA
SHC
CA
SHC
CA
SHC
CA
SHC
CA
SHC
40 (4.5)
4.0
2.9
4.1
3.0
4.4
3.0
4.5
3.2
4.7
3.2
5.0
3.1
5.4
3.1
63 (7.1)
6.3
4.6
6.5
4.7
6.9
4.7
7.1
4.9
7.4
4.9
7.9
4.9
8.5
4.8
100 (11.2)
10.0
7.1
10.2
7.2
11.0
7.2
11.2
7.5
11.7
7.6
12.5
7.5
13.4
7.4
125 (14.0)
12.5
8.8
12.8
9.0
13.7
9.0
14.0
9.4
14.7
9.4
15.7
9.3
16.7
9.2
* The capacity does not depend on the outdoor temperature.
kcal/h = kW x 860, BTU/h = kW x 3,412
PCFY-P-VKM-E
CA: Capacity (kW), SHC: Sensible Heat Capacity (kW)
Model size (Rated kW)
Indoor air temp.
21.5°C D.B.
23°C D.
B.
25°C D.
B.
27°C D.
B.
28°C D.
B.
30°C D.B.
32°C D.B.
15°C W.
B.
16°C W.B.
18°C W.B.
19°C W.B.
20°C W.B.
22°C W.B.
24°C W.B.
CA
SHC
CA
SHC
CA
SHC
CA
SHC
CA
SHC
CA
SHC
CA
SHC
40 (4.5)
3.9
2.9
4.1
3.0
4.4
3.0
4.5
3.2
4.7
3.1
5.0
3.1
5.3
3.1
63 (7.1)
6.2
4.5
6.4
4.6
6.9
4.6
7.1
4.9
7.4
4.9
7.9
4.8
8.3
4.8
1
0
0
(
1
1
.
2
)
9
.
8
7
.
0
1
0
.
1
7
.
2
1
0
.
9
7
.
2
1
1
.
2
7
.
5
1
1
.
6
7
.
5
1
2
.
4
7
.
5
1
3
.
2
7
.
4
125 (14.0)
12.3
8.7
12.7
8.9
13.6
8.9
14.0
9.4
14.5
9.4
15.5
9.3
16.5
9.1
* The capacity does not depend on the outdoor temperature.
kcal/h = kW x 860, BTU/h = kW x 3,412