1 - 280
CT
MEE15K022
5. Cooling [Ceiling cassette (4-way flow type)]
YKB/YLM 2nd
PLFY-P-VBM-E
CA: Capacity (kW), SHC: Sensible Heat Capacity (kW)
Model size (Rated kW)
Indoor air temp.
21.5°C D.B.
23°C D.
B.
25°C D.
B.
27°C D.
B.
28°C D.
B.
30°C D.B.
32°C D.B.
15°C W.
B.
16°C W.B.
18°C W.B.
19°C W.B.
20°C W.B.
22°C W.B.
24°C W.B.
CA
SHC
CA
SHC
CA
SHC
CA
SHC
CA
SHC
CA
SHC
CA
SHC
20 (2.2)
2.0
1.9
2.0
2.0
2.2
2.0
2.2
2.1
2.3
2.1
2.5
2.1
2.6
2.1
25 (2.8)
2.5
2.3
2.6
2.3
2.7
2.3
2.8
2.5
2.9
2.5
3.1
2.5
3.3
2.4
32 (3.6)
3.2
2.7
3.3
2.8
3.5
2.8
3.6
3.0
3.8
3.0
4.0
3.0
4.3
2.9
40 (4.5)
4.0
3.3
4.1
3.4
4.4
3.4
4.5
3.6
4.7
3.6
5.0
3.6
5.4
3.6
50 (5.6)
5.0
3.8
5.1
3.9
5.5
3.9
5.6
4.1
5.9
4.2
6.3
4.1
6.7
4.1
63 (7.1)
6.3
4.7
6.5
4.8
6.9
4.8
7.1
5.0
7.4
5.1
7.9
5.0
8.5
5.0
80 (9.0)
8.0
5.9
8.2
6.0
8.8
6.0
9.0
6.3
9.4
6.3
10.1
6.2
10.7
6.2
100 (11.2)
10.0
7.3
10.2
7.5
11.0
7.5
11.2
7.8
11.7
7.9
12.5
7.8
13.4
7.7
125 (14.0)
12.5
8.9
12.8
9.1
13.7
9.0
14.0
9.5
14.7
9.5
15.7
9.4
16.7
9.3
* The capacity does not depend on the outdoor temperature.