6. CAPACITY TABLES
DATA G10
OUTDOOR UNITS
HP
6. CAPACITY TABLES
6-1. Correction by temperature
CITY MULTI could have varied capacity at different designing temperature. Using the nominal cooling/heating capacity value and
the ratio below, the capacity can be observed at various temperature.
Nominal
Cooling
Capacity
Input
kW
BTU/h
kW
Nominal
Heating
Capacity
Input
kW
BTU/h
kW
PUHY-
HP200YHM
HP250YHM
PUHY-
HP200YHM
HP250YHM
22.4
76,400
6.40
28.0
95,500
9.06
Nominal
Cooling
Capacity
Input
kW
BTU/h
kW
PUHY-
HP400YSHM
HP500YSHM
45.0
153.500
12.86
56.0
191,100
18.16
Nominal
Heating
Capacity
Input
kW
BTU/h
kW
PUHY-
HP400YSHM
HP500YSHM
50.0
170,600
13.35
63.0
215,000
18.04
25.0
85,300
6.52
31.5
107,500
8.94
Ratio of cooling capacity and power input
Outdoor temperature
Ratio of heating capacity and power input
Outdoor temperature
-5
0
5
10
15
20
25
30
35
40
45
23
32
41
50
59
68
77
86
95
104
113
1.1
1.2
1.0
0.9
0.8
0.7
0.6
0.5
Ratio of power input
-25
-20
-15
-10
-5
0
5
10
15
Ratio of power input
1.3
1.2
1.0
0.9
0.8
0.7
0.6
1.1
Ratio of cooling capacity
Indoor Temperature
Ratio of heating capacity
0.6
0.9
1.0
1.1
1.2
1.3
1.4
1.5
1.6
1.7
1.8
1.9
2.0
0.8
0.7
0.6
0.5
1.3
1.4
1.2
1.0
0.9
0.8
0.7
1.1
Indoor Temperature
-4
-13
5
1
4
2
3
3
2
4
1
5
0
5
9