4. Outdoor Installation
YKB/YLM 2nd
4 - 112
S.D. R2
MEE15K022
4-3. Piping direction
4-3-1. Lifting method
·
 When lifting the unit with ropes, run the ropes under the unit and use the lifting hole.
·
 Support the unit at four points with two ropes, and avoid giving mechanical shock.
·
 Suspension rope angle must be 40° or less, so as to avoid compressing fan guard.
·
 Use two ropes, each at least 8m [26 ft.] in length
·
 Use ropes strong enough to support the weight of the unit.
·
Always suspend the unit from four corners. (It is dangerous to suspend a unit from two corners and must not be attempt-
ed.)
·
 Use protective pads to keep the ropes from scratching the panels on the unit.
·
 Products weighing more than 20 kg [45 LBS] should not be carried alone.
·
 Do not carry the product by the PPbands.
·
T
o avoid the risk of injury, do not touch the heat exchanger fins.
·
 Plastic bags may pose a risk of choking hazard to children. Tear plastic bags into pieces before disposing of them.
·
 When lifting and transporting outdoor units with ropes, run the ropes through lifting hole at the unit base. Securely
fix the unit so that the ropes will not slide off, and always lift the unit at four points to prevent the unit from falling.
Exercise caution when transporting products.
CAUTION
Sling holes
(two each in the front and back)
P450, 500
EP400, 450, 500
3
·
 Use a 50mm [1-31/32 in.] or thicker cardboard or cloth as a protective pad on the top of the unit to prevent contact
between the fan guard and slings.
Slings
Protective pads
(Min. 8m [26 ft.] x 2)
Fan guard
50mm [1-31/32 in.] or
thicker protective pads
(two each in the
 front and back)
(two each in the
 front and back)
1
P200, 250
EP200, 250
40°
Slings
Protective pads
(Min. 8m [26 ft.] x 2)
Fan guard
Sling holes
(two each in the front and back)
50mm [1-31/32 in.] or
thicker protective pads
(two each in the
 front and back)
(two each in the
 front and back)
Sling holes
(two each in the front and back)
40°
2
P300, 350, 400
EP300, 350
Slings
Fan guard
(Min. 8m [26 ft.] x 2)
(two each in the
 front and back)
50mm [1-31/32 in.] or
thicker protective pads
(two each in the
 front and back)
40°
Protective pads