1 .. 888 889 890 891 892 893 894 895 896 897 898 .. 908
4. Outdoor Installation
YKB/YLM 2nd
4 - 110
S.D. R2
MEE15K022
4-2. Spacing
(1) Walls are lower than the height limit.
• Secure enough space around the unit as shown in the figure.
In case of single installation
(2) If the wall height (H) of the front, rear or side exceeds the wall height restriction
(3) If there are obstacles at the upper part of the unit
• If the wall height exceeds the height limit, widen the space labeled "L" and "W" by the amount that exceeds the limit (labeled <h> in the figure).
500 [19-11/16]
450 [17-23/32]
L
W
W
Minimum space behind the unit
Minimum space on both sides of the unit
Condition
100 [3-15/16]
300 [11-13/16]
50 [1-31/32]
15 [19/32]
L
W
Minimum space behind the unit
Minimum space on both sides of the unit
Condition
100 [3-15/16] + h
300 [11-13/16] + h
50 [1-31/32] + h
15 [19/32] + h
L
W
Should be shorter than
the unit height
Should be shorter than
the unit height
h
500
[19-11/16]
500 [19-11/16]
500 [19-11/16]
450 [17-23/32] + h
450 [17-23/32] + h
450 [17-23/32] + h
L
W
W
h
L
W
W
h
h
h
L
W
W
h
Should be shorter than
the unit height
Should be shorter than
the unit height
Should be shorter than
the unit height
Should be shorter than
the unit height
Should be shorter than
the unit height
Should be shorter than
the unit height
240 [9-15/32]
45°
50 [1-31/32]
1000 [39-3/8]
Air deflector grills
(field supplied)
(Unit : mm [in.])