1 .. 759 760 761 762 763 764 765 766 767 768 769 .. 908
3 - 93
Controller
MEE15K022
3. System remote controller
YKB/YLM 2nd
 
(2). Parts Purchased Separately
 
 
Prepare the following parts to install this device.
[Parts to be Purchased Separately]
[Commercially available parts]
Required Part
Specification
Unit fixing screws
M4 screw    4 (*M4: ISO metric screw thread)
Power supply for this
device
Commercially available power source: 24 VDC   10% 0.2 A (Minimum loading), SEL
V circuit, power line with
grounding terminal
Ripple noise: Lower than 200 mVp-p
Compatible specification
Authorized or CE marked products
Subject to regulations:
- IEC60950 (or EN60950)
- CISPR22/24 (or EN55022/24)
- IEC61000-3-2/3-3 (or EN61000-3-2/3-3)
When using transistor output (including extension output) for the 24 VDC output of this device, increase
the capacity to match the number used.
• 1 set used: 0.3 ADC (Minimum)
• 2 sets used: 0.4 ADC (Minimum)
3 sets used: 0.5 ADC (Minimum)
• 4 sets used: 0.6 ADC (Minimum)
• 5 sets used: 0.7 ADC (Minimum)
6 sets used: 0.8 ADC (Minimum)
* The increase of the power supply capacity is 0.1 ADC for every set.
Power line
Use a sheathed vinyl cord or cable. At least 0.75 mm
2
 (AWG18)
M-NET transmission
line
Type of the cable: Sheathed vinyl cords or cable which comply with the following specifications or
equivalent.
• CPEV
1.2 mm to
1.6 mm • CVVS 1.25 mm
2
 to 2 mm
2
 (AWG 16 to 14)
* CPEV: PE insulated PVC jacketed shielded communication cable
* CVVS: PVC insulated PVC jacketed shielded control cable
PE: Polyethylene    PVC: Polyvinyl choloride
Power needs to be supplied to the M-NET circuitry of this device. Use an outdoor unit or a separately
purchased power supply unit for the transmission line.
Signal lines
Use electric wire of an appropriate size for the terminal block of this device.
Electric wire size
····
(1)
Solid wire:
0.65 mm (AWG21) -
1.2 mm (AWG16)
(2)
Stranded wire:
0.75 mm
2
 (AWG18) - 1.25 mm
2
 (AWG16)
Single strand: At least
0.18 mm
T
o use an expansion input/output, use a separa
tely purchased external input/output adapter.
Name
Model
Application
Remark
Power supply unit
PAC-SC51KUA
Power supply to the M-NET transmission line
This is not required when power is to be
supplied from an outdoor unit.
External I/O adapter
PAC-YG10HA-E
Connection adapter for using an expansion
input/output
This is required when an expansion input/
output is used.
Name
Application
Remark
External 24 VDC
power source
Supplies power when to use the DIDO controller or
transistor output.
Refer to "Power supply for this device" in "Required
Part" above for the power supply capacity.
Relay device
Requires commercially available relay device
depending on the electric specifications with an
external device.