1 .. 758 759 760 761 762 763 764 765 766 767 768 .. 908
3 - 92
Controller
MEE15K022
3. System remote controller
YKB/YLM 2nd
*This figure omits the power supply line and only shows the transmission line.
For example, 5 contacts connected to the DIDO controller are calculated as the equivalent of 5 indoor units connected to
AE-200E/AE-50E/EW-50E/AG-150A/EB-50GU-J.
<Restrictions>
Maximum of 50 units (50 channels) per AE-200E/AE-50E/EW-50E/AG-150A/EB-50GU-J
However, the number of units that can be connected to a AE-200E/AE-50E/EW-50E/AG-150A/EB-50GU-J is up to 50 including
the number of contacts used on this device, an indoor unit, LOSSNAY unit, etc.
Up to 6 contacts can be connected to the DIDO controller (1 M-NET address). One contact connected to this device is calculated as
the equivalent of one indoor unit connected to AE-200E/AE-50E/EW-50E/AG-150A/EB-50GU-J.
NOTE
• For the shield ground of the M-NET centralized control line, use single-point grounding at the power unit for
the transmission line.
However, when supplying electric power to the M-NET centralized control line from the R410A series outdoor
unit
*1
 without using a power supply unit for the transmission line, use single-point grounding at the TB7 of that
outdoor unit. *1: Except PUMY model.
Furthermore, when connecting this device to the M-NET indoor control line, use grounding at the TB3 for each
outdoor unit system.
• If the M-NET transmission line of this device is connected to the M-NET indoor control line and the outdoor
unit is down because, for example, the power supply is interrupted for servicing or there is a failure, the DIDO
controller cannot be controlled from the system controller.
• Controlling the ON/OFF remote controller is only possible with channel 1 of a standard terminal block.   
• When AE-200E/AE-50E/EW-50E/AG-150A/EB-50GU-J is connected, monitoring control can only be
   performed from AE-200E/AE-50E/EW-50E/AG-150A/EB-50GU-J Web or TG-2000A. Monitoring control
   cannot be performed from the ON/OFF  remote controller
.
(a) ON/OFF
, (ON) output
(b) (OFF) output
(c) ON/OFF input
(d) Error/Normal input
Standard: Terminal block (for 2 units)
Expansion: Connectors (for 4 units)
Total: 6 units
(c)(d)
M-NET
M-NET
LAN
(a)
(b)
(a)
(b)
(c)
(d)
Indoor control line
DIDO controller
or
ON/OFF remote controller
DIDO control
Ventilation fan,
lighting, etc.
× up to 6 units
Ventilation fan,
lighting, etc.
24 VDC
Power supply
24 VDC
Power supply
× up to 6 units
CITY MULTI
AE-200E
(EW-50E)
AE-200E
(EW-50E)