1 .. 6 7 8 9 10 11 12 13 14 15 16 .. 80
2 - 125
1. SPECIFICATIONS
DATA G10
OUTDOOR UNITS
Y (HIGH COP)
 Model
PUHY-EP700YSJM-A(-BS)
 Power source
3-phase 4-wire 380-400-415V 50/60Hz
 Cooling capacity
*1
kW
80.0
 (Nominal)
*1
kcal/h
68,800
*1
BTU/h
273,000
Power input
kW
19.13
Current input
A
32.2-30.6-29.5
COP
kW/kW
4.18
 Temp.
 range of
Indoor
W.
B.
15.0~24.0°C(59~75°F)
 cooling
Outdoor
D.B.
-5.0~46.0°C(23~115°F)
 Heating capacity
*2
kW
88.0
 (Nominal)
*2
kcal/h
75,700
*2
BTU/h
300,300
Power input
kW
20.00
Current input
A
33.7-32.0-30.9
COP
kW/kW
4.40
 Temp.
 range of
Indoor
D.
B.
15.0~27.0°C(59~81°F)
 heating
Outdoor
W.
B.
-20.0~15.5°C(-4~60°F)
 Indoor unit
Total capacity
50~130 % of outdoor unit capacity
 connectable
Model/Quantity
P15~P250/1~50
 Sound pressure level (measured in anechoic room)
dB <A>
63.5
 Power pressure level (measured in anechoic room)
dB <A>
83.5
 Refrigerant
Liquid pipe
mm (in.
)
19.05(3/4) Brazed
piping diameter
Gas pipe
mm (in.
)
34.93(1-3/8) Brazed
 Set Model
 Model
PUHY-EP200YJM-A(-BS)
PUHY-EP200YJM-A(-BS)
PUHY-EP300YJM-A(-BS)
 FAN
Type x Quantity
Propeller fan x 1
Propeller fan x 1
Propeller fan x 2
Air flow rate
m
3
/min
170
170
370
L/s
2,833
2,833
6,167
cfm
6,003
6,003
13,065
Control , Driving mechanism
Inverter-control, Direct-driven by motor
Inverter-control, Direct-driven by motor
Inverter-control, Direct-driven by motor
Motor output
 kW
0.46 x 1
0.46 x 1
0.46 x 2
*3
External static press.
0 Pa (0 mmH
2
O)
0 Pa (0 mmH
2
O)
0 Pa (0 mmH
2
O)
 Compressor
Type x Quantity
Inverter scroll hermetic compressor
Inverter scroll hermetic compressor
Inverter scroll hermetic compressor
Manufacture
AC&R Works, MITSUBISHI ELECTRIC
CORPORATION
AC&R Works, MITSUBISHI ELECTRIC
CORPORATION
AC&R Works, MITSUBISHI ELECTRIC
CORPORATION
Starting method
Inverter
Inverter
Inverter
Motor output
kW
5.4
5.4
7.7
Case heater
kW
0.035
0.035
0.045
Lubricant
MEL32
MEL32
MEL32
 External finish
Pre-coated galvanized steel sheets
(+powder coating for -BS type)
Pre-coated galvanized steel sheets
(+powder coating for -BS type)
Pre-coated galvanized steel sheets
(+powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar>
<MUNSELL 5Y 8/1 or similar>
<MUNSELL 5Y 8/1 or similar>
 External dimension HxWxD
mm
1,710(1,650 without legs) x 920 x 760
1,710(1,650 without legs) x 920 x 760
1,710(1,650 without legs) x 1,750 x 760
in.
67-3/8(65 without legs) x 36-1/4 x 29-15/
16
67-3/8(65 without legs) x 36-1/4 x 29-15/
16
67-3/8(65 without legs) x 68-15/16 x 29-
15/16
 Protection  devices
High pressure protection
High pressure sensor, High pressure
switch at 4.15MPa (601 psi)
High pressure sensor, High pressure
switch at 4.15MPa (601 psi)
High pressure sensor, High pressure
switch at 4.15MPa (601 psi)
Inverter circuit (COMP./FAN)
Over-heat protection, Over-current pro-
tection
Over-heat protection, Over-current pro-
tection
Over-heat protection, Over-current pro-
tection
Compressor
Over-heat protection
Over-heat protection
Over-heat protection
Fan motor
Thermal switch
Thermal switch
Thermal switch
 Refrigerant
Type x original charge
R410A x 8.0kg (18lbs)
R410A x 8.0kg (18lbs)
R410A x 11.8kg (27lbs)
Control
LEV and HIC circuit
 Net weight
 kg (lbs)
200(441)
200(441)
290(640)
 Heat exchanger
Salt-resistant cross fin & copper tube
Salt-resistant cross fin & copper tube
Salt-resistant cross fin & copper tube
 HIC circuit (HIC: Heat Inter-Changer)
Copper pipe,tube-in-tube structure
Copper pipe,tube-in-tube structure
Copper pipe,tube-in-tube structure
 Pipe between unit and
Liquid pipe
mm (in.
)
9.52(3/8) Brazed
9.52(3/8) Brazed
12.7(1/2) Brazed
 distributor
Gas pipe
mm (in.
)
19.05(3/4) Brazed
19.05(3/4) Brazed
22.2(7/8) Brazed
 Defrosting method
Auto-defrost mode (Reversed refrigerant cycle)
 Drawing
External
WKD94G085
Wiring
KE94C449
KE94C449
KE94C450
 Standard attachment
Document
Installation Manual
Accessory
Refrigerant conn. pipe
 Optional parts
Outdoor Twinning kit: CMY-Y300VBK2/3
Joint: CMY-Y102SS/LS-G2, CMY-Y202S/302S-G2
Header: CMY-Y104/108/1010-G
 Remarks
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be re-
ferred to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.
Notes :
Unit converter
 1.Nominal cooling conditions(subject to JIS B8615-2)
 Indoor:27°CDB/19°CWB(81°FDB/66°FWB), Outdoor:35°CDB(95°FDB)
 Pipe length:7.5m(24-9/16ft.), Level difference:0m(0ft.)
  2.Nominal heating conditions(subject to JIS B8615-2)
 Indoor:20°CDB(68°FDB), Outdoor:7°CDB/6°CWB(45°FDB/43°FWB)
 Pipe length:7.5m(24-9/16ft.), Level difference:0m(0ft.)
  3.External static pressure option is available (30Pa, 60Pa/3.1mmH
2
O, 6.1mmH
2
O).
kcal
=kW x 860
  BTU/h
=kW x 3,412
cfm
=m
3
/min x 35.31
lbs
=kg/0.4536
 *Above specification data is
 subject to rounding variation.