1 .. 72 73 74 75 76 77 78 79 80 81 82 .. 86
2 - 105
6. CAPACITY TABLES
DATA G10
OUTDOOR UNITS
Y
6-3-2. Heating capacity correction
6-3-3. How to obtain the equivalent piping length
0.90
0
20
40
60
80
100
120
140
160
180
Heating capacity correction factor
0.95
1.00
Piping equivalent length (m)
PUHY-(E)P200,250YJM-A
0.90
0
20
40
60
80
100
120
140
160
180
Heating capacity correction factor
0.95
1.00
Piping equivalent length (m)
PUHY-(E)P700,750,800YSJM-A(1)
0.90
0
20
40
60
80
100
120
140
160
180
Heating capacity correction factor
0.95
1.00
Piping equivalent length (m)
PUHY-(E)P300,350,400,450Y(S)JM-A
0.90
0
20
40
60
80
100
120
140
160
180
Heating capacity correction factor
0.95
1.00
Piping equivalent length (m)
PUHY-(E)P850,900,950,1000YSJM-A
0.90
0
20
40
60
80
100
120
140
160
180
Heating capacity correction factor
0.95
1.00
Piping equivalent length (m)
PUHY-(E)P500,550,600,650YSJM-A(1)
0.85
0.90
0
20
40
60
80
100
120
140
160
180
Heating capacity correction factor
0.95
1.00
Piping equivalent length (m)
PUHY-P1050,1100,1150,1200,1250YSJM-A
1   PUHY
-(E)P200YJM
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.35 x number of bends in the piping) m
2   PUHY
-(E)P250,300YJM
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.42 x number of bends in the piping) m
3   PUHY
-P350YJM
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.47 x number of bends in the piping) m
4   PUHY
-(E)P400,450,500,550,600,650Y(S)JM
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.50 x number of bends in the piping) m
5   PUHY
-(E)P700,750,800YSJM
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.70 x number of bends in the piping) m
6   PUHY
-(E)P850,900,950,1000,1050,1100,1
150,1200,1250YSJM
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.80 x number of bends in the piping) m