7. CAPACITY TABLES
DATA G10
OUTDOOR UNITS
2 - 20
S
7. CAPACITY TABLES
7-1. Correction by temperature
CITY MULTI could have various capacities at different designing temperatures. Using the nominal cooling/heating capacity values
and the ratios below, the capacity can be found for various temperatures.
Ratio of cooling capacity and power input
Outdoor temperature
Ratio of heating capacity and power input
Outdoor temperature
-5
0
5
10
15
20
25
30
35
40
45
23
32
41
50
59
68
77
86
95
104
113
°CDB
°FDB
1.2
1.1
1.0
0.8
0.9
0.7
0.6
0.5
0.4
Ratio of power input
-20
-4
-15
5
-10
14
-5
23
0
32
5
41
10
50
15
59
°CWB
°FWB
0.6
1.0
0.8
0.9
0.7
0.6
0.5
0.4
Ratio of power input
1.4
1.3
1.1
1.0
0.9
1.2
Ratio of cooling capacity
Indoor Temperature
22°CWB
72°FWB
20°CWB
68°FWB
18°CWB
64°FWB
16°CWB
61°FWB
22°CWB
72°FWB
20°CWB
68°FWB
18°CWB
64°FWB
16°CWB
61°FWB
1.3
1.2
1.0
0.9
0.8
0.7
1.1
Ratio of heating capacity
15°CDB
59°FDB
20°CDB
68°FDB
25°CDB
77°FDB
15°CDB
59°FDB
20°CDB
68°FDB
25°CDB
77°FDB
Indoor Temperature
Nominal
Cooling
Capacity
Input
kW
kcal/h
Btu/h
kW
Nominal
Cooling
Capacity
Input
kW
kcal/h
Btu/h
kW
Nominal
Heating
Capacity
Input
kW
kcal/h
Btu/h
kW
Nominal
Heating
Capacity
Input
kW
kcal/h
Btu/h
kW
PUMY-
P100YHMB
P125YHMB
11.2
9,600
38,200
3.30
14.0
12,000
47,800
4.27
PUMY-
P140YHMB
15.5
13,300
52,900
5.32
PUMY-
P100YHMB
P125YHMB
12.5
10,800
42,700
3.63
16.0
13,800
54,600
4.29
PUMY-
P140YHMB
18.0
15,500
61,400
5.32