2. M-NET control
YKB/YLM 2nd
4 - 94
S.D. R2
MEE15K022
2-4-3-12.
LM-AP
LM-AP(01)
PC
LONWORKS
®
card
LONWORKS
®
card
LONWORKS
®
card
For other equipments (Lighting, security, elevator etc.)
LM-AP can transmit for max.
50 indoor units in single-refrigerant-system or multi-refrigerant-system.
DipSW1-2
OFF
247
L
ON
W
ORKS
®
000
AE-200E
identified by Neuron ID
LM-AP(02)
DipSW1-2
ON
247
identified by Neuron ID
<Two outdoor units>
<One outdoor unit>
CN41
CN40
CN41
CN40
LM-AP can transmit for max. 50 indoor units;
If system controller (SC) is used, DipSW1-2 at LM-AP and DipSW5-1 at Outdoor unit should set to "ON".
Change Jumper from CN41 to CN40 to activate power supply to LM-AP itself for those LM-AP connected without system
controller (SC).
Indoor unit
MA R/C
MA R/C
(Main)
(Sub)
MA R/C
SRU
Wireless R/C
*1
*1
01
02
03
42
TB15
TB5
BC controller
53
TB02
TB5
TB5
TB2
Transmission Booster
PAC-SF46EPA
TB5
TB15
TB15
TB3
TB15
Group 2
Group 1
Group 40
TB7
TB7
TB7
TB3
TB3
52
51
OC
OS
TB3
51
OC
CN41
CN40
CN41
CN40
CN41
CN40
OFF
DipSW5-1
OFF
DipSW5-1
OFF
DipSW5-1
Indoor unit
ME R/C
ME R/C
ME R/C
01
02
03
30
TB5
BC controller
(Main)
53
TB02
BC controller
(Sub)
80
BC controller
(Sub)
94
TB02
TB02
BC controller
(Main)
93
TB02
TB5
TB5
TB2
Transmission Booster
PAC-SF46EPA
TB5
ME R/C
101
102
130
180
TB3
Group 2
Group 1
Group 21
TB3
TB7
TB7
TB7
TB7
TB7
TB3
52
51
OC
OS
TB3
TB3
92
91
OC
OS
TB3
97
OC
CN41
CN40
CN41
CN40
CN41
CN40
CN41
CN40
CN41
CN40
ON
DipSW5-1
ON
DipSW5-1
ON
DipSW5-1
ON
DipSW5-1
ON
DipSW5-1
ME R/C
ME R/C
Indoor unit
ME R/C
ME R/C
142
144
145
195
41
42
43
44
45
TB5
TB5
LOSSNA
Y
TB5
TB5
TB5
Group 33
Group 32
Group 31
Group 34
Group 35
ME R/C
141
PURY
PURY
PURY
PURY
PURY
*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
*2 When a PAR-31MAA(E) is connected to a group, no other MA remote controllers can be connected to the same group.
LOSSNAY
remote
controller
46
TB5
TM4
LOSSNAY
Group 36