1 .. 850 851 852 853 854 855 856 857 858 859 860 .. 908
1. Electrical work
YKB/YLM 2nd
4 - 72
S.D. R2
MEE15K022
1-2-3. Electrical characteristics of BC controller
Symbols: MCA (Max. Circuit Amps), MFA (Max. Fuse Amps), RLA (Rated Load Amps)
BC controller
Power supply
RLA(A)
Hz
Volts
Range+-10%
MCA(A)
MFA(A)
CMB-P104V-G1
50/60
220
Max.
: 264V
Min.: 198V
0.45
15
0.31
230
0.34
240
0.36
CMB-P105V-G1
220
0.55
0.38
230
0.41
240
0.44
CMB-P106V-G1
220
0.65
0.45
230
0.48
240
0.52
CMB-P108V-G1
220
0.85
0.58
230
0.63
240
0.68
CMB-P1010V-G1
220
1.04
0.71
230
0.77
240
0.83
CMB-P1013V-G1
220
1.34
0.92
230
1.00
240
1.07
CMB-P1016V-G1
220
1.63
1.12
230
1.22
240
1.30
CMB-P108V-GA1
220
0.85
0.58
230
0.63
240
0.68
CMB-P1010V-GA1
220
1.04
0.71
230
0.77
240
0.83
CMB-P1013V-GA1
220
1.34
0.92
230
1.00
240
1.07
CMB-P1016V-GA1
220
1.63
1.12
230
1.22
240
1.30
CMB-P1016V-HA1
220
1.63
1.12
230
1.22
240
1.30
CMB-P104V-GB1
220
0.40
0.28
230
0.30
240
0.32
CMB-P108V-GB1
220
0.79
0.55
230
0.59
240
0.63
CMB-P1016V-HB1
220
1.58
1.08
230
1.17
240
1.26