4 - 26
S.D. Y
MEE15K022
2. M-NET control
YKB/YLM 2nd
2-4-3. System examples
Factory setting
Setting at the site
Original switch setting of the outdoors, indoors, controllers, LM-AP and BM ADAPTER  at shipment is as follows.
  Outdoor unit
 
: Address:   00, CN41: ON (Jumper), DipSW5-1: OFF
  Indoor unit
 
: Address:   00
  ME remote controller
: Address: 101
  LM-AP
 
: Address: 247, CN41: ON (Jumper), DipSW1-2: OFF
  BM ADAPTER
: Address: 000, CN41: ON (Jumper)
  
AE-200E/AE-50E/EW
-50E
: Address: 000, CN21: ON (Jumper)
  DipSW5-1(Outdoor)
: When the System Controller is used, all the Dip SW5-1 at the outdoor units should be
 
 
 
  set to "ON".   * Dip SW5-1 remains OFF when only LM-AP is used.
  DipSW1-2(LM-AP)
: When the LM-AP is used together with System Controller, DipSW1-2 at the LM-AP should be
 
 
 
  set to "ON".
  CN40/CN41
 
: Change jumper from CN41 to CN 40 at outdoor control board will activate central transmission
 
 
 
  power supply to TB7;
 
 
 
  (Change jumper at only one outdoor unit when activating the transmission power supply
 
 
 
    without using a power supply unit.)
 
 
 
  Change jumper from CN41 to CN 40 at LM-AP/BM ADAPTER will activate transmission power
supply to LM-AP/BM ADAPTER itself;
 
 
 
  Power supply unit is recommended to use for a system having more than 1 outdoor unit,
 
 
 
  because the central transmission power supply from TB7 of one of outdoor units is risking that
 
 
 
  the outdoor unit failure may let down the whole system controller system.
  CN21
(AE-200E/AE-50E/EW-50E)
: Activates the power supply to M-NET transmission line from AE-200E/AE-50E/EW-50E
(CN21: ON (power supplied), OFF (power not supplied)
2-4-3-1. MA remote controller, Single-refrigerant-system, No System Controller
1. Outdoor units OC, OS1 and OS2 in one refrigerant circuit system are automatically detected.
    OC, OS1 and OS2 are ranked in descending order of capacity. If units are the same capacity
, they are ranked in ascending order
    of their address.
2. No address setting is needed.
3. For a system having more than 32 indoor unit (P15-P140), confirm the need of Booster at
2-3 "System configuration
    
restrictions".
4. When a PAR-31MAA(E) is connected to a group, no other MA remote controllers can be connected to the same group.
NOTE:
Indoor unit
MA R/C
MA R/C
MA R/C
(Main)
(Sub)
MA R/C
SRU
Wireless R/C
1*
*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
1*
00
00
00
00
00
TB15
TB5
TB5
TB5
TB5
TB5
TB15
TB15
TB15
TB15
Group 2
Group 1
Group 3
Group 4
<Three outdoor units>
<Two outdoor units>
<One outdoor unit>
TB3
TB3
TB3
00
00
00
OC
OS1
OS2
PUHY
TB3
TB3
00
00
OC
OS1
PUHY
TB3
00
OC
CN41
CN40
CN41
CN40
CN41
CN40
CN41
CN40
CN41
CN40
CN41
CN40
OFF
DipSW5-1
OFF
DipSW5-1
OFF
DipSW5-1
OFF
DipSW5-1
OFF
DipSW5-1
OFF
DipSW5-1
PUHY