1 .. 796 797 798 799 800 801 802 803 804 805 806 .. 908
4 - 18
S.D. Y
MEE15K022
1. Electrical work
YKB/YLM 2nd
The local standards and/or regulations is applicable at a higher priority.
1-4-6. PUHY
-EP650, 700, 750, 800, 850, 900, 950,
                          1000, 1050, 1
100, 1150, 1200, 1250, 1300, 1350YSLM-A1
Note4
Note3
Note3
Connector
CN41   CN40
Central control
transmission cable
>=1.25mm
2
Shield cable
(CVVS, CPEVS
  MVVS)
TB7
(S)
TB7
(S)
TB1
(L1,L2,L3)
TB3
(M1,M2)
TB7
  (M1,M2)
TB3
(M1,M2)
TB7
 (M1,M2)
SC
OU
OU
Note3
TB7
(S)
TB1
(L1,L2,L3)
TB3
(M1,M2)
TB7
  (M1,M2)
OU
Note4
To other OU
<In the case a system controller is connected.>
To *1 or *2
*1
Power supply
1-phase
220-240V 50/60Hz
Note10
Indoor-outdoor
transmission cable
>=1.25mm
2
Shield cable
(Using MA remote controller)
Connecting TB5 terminal.
Note12
TB1
(L1,L2,L3)
Note7
Power supply
1-phase
220-240V 50/60Hz
TB5
(M1,M2)
TB2
(L,N)
S
TB15
(1,2)
TB5
(M1,M2)
TB2
(L,N)
S
TB15
(1,2)
TB5
(M1,M2)
TB2
(L,N)
S
S
S
E
TB15
(1,2)
TB5
(M1,M2)
TB2
(L,N)
TB1
(R,S)
TB2
TB3
S
TB15
(1,2)
Transmission
booster
Note8
Note9
MA R/C
MA R/C
MA R/C
MA R/C cable
0.3-1.25mm
2
(0.75~1.25mm
2
)
<=200m
Note5, Note1
1
IU
(Shield)
(Shield)
(Shield)
(Shield)
(Shield)
(Shield)
Note6
Note7
Pull box
Power supply
3-phase 4-wire
380-400-450V
50/60Hz
Note10,13
Power supply
3-phase 4-wire
380-400-450V
50/60Hz
Note10,13
Power supply
3-phase 4-wire
380-400-450V
50/60Hz
Note10,13
*2
Indoor-outdoor
transmission cable
>=1.25mm
2
Shield cable
(Using ME remote controller)
Connecting TB5 terminal.
Power supply
1-phase
220-240V 50/60Hz
ME R/C
ME R/C
ME R/C
ME R/C cable
0.3~1.25mm
2
(0.75~1.25mm
2
)
<=10m
Note5, Note11
Note6
Note7
Note7
Power supply
1-phase
220-240V 50/60Hz
Note10
TB5
(M1,M2)
TB2
(L,N)
S
TB15
(1,2)
TB5
(M1,M2)
TB2
(L,N)
S
TB15
(1,2)
TB5
(M1,M2)
TB2
(L,N)
S
S
S
E
TB15
(1,2)
TB5
(M1,M2)
TB2
(L,N)
TB1
(R,S)
TB2
TB3
S
TB15
(1,2)
Transmission
booster
Note8
Note9
IU
(Shield)
(Shield)
(Shield)
(Shield)
(Shield)
(Shield)
Pull box
GFI
LW
WB
GFI
LW
WB
GFI
LW
WB
GFI
LW
WB
GFI
LW
WB
GFI
LW
WB
GFI
LW
WB
*1  The Ground-fault interrupter should support Inverter circuit. (e.g. Mitsubishi Electric's NV-S series or equivalent).
*2  Ground-fault interrupter should combine using of local switch or wiring breaker.
*3  It shows data for B-type fuse of the breaker for current leakage.
*4  If a large electric current flows due to malfunction or faulty wiring, earth-leakage breakers on the unit side and on the centralized controller side
may both operate.
Depending on the importance of the system, separate the power supply system or take protective coordination of breakers.
Local switch
Minimum  Wire thickness
Earth wire
<mm
2
>
Power wire
<mm
2
>
Wiring breaker*4
(NFB)
<A>
OCP*3, *4
<A>
BKC
<A>
Symbol
GFI
LW
BKC
OCP
WB
NFB
OU
IU
SC
MA R/C
ME R/C
Ground-fault interrupter
Local switch
Breaker capacity
Over-current protector
Wiring breaker
Non-fuse breaker
Outdoor unit
Indoor unit
System controller
MA remote controller
ME remote controller
Note:  
1  The transmission cable is not-polarity double-wire.
2  Symbol      means a screw terminal for wiring.
3  The shield wire of transmission cable should be connected to the grounding terminal at
Outdoor unit. All shield wire of M-Net transmission cable among Indoor units should be
connected to the S terminal at Indoor unit or all shield wire should be connected together.  
The broken line at the scheme means shield wire.
4  When the Outdoor unit connected with system controller, power-supply to TB7 of the
outdoor unit(s) is needed. The connector change from CN41 to CN40 at one of the
outdoor units will enable the outdoor unit to supply power to TB7, or an extra power
supplying unit PAC-SC51KUA should be used. The transmission cable (above 1.25mm
2
,
shielded, CVVS/CPEVS/MVVS) among Outdoor units and system controllers is called
central control transmission cable. The shield wire of the central control transmission
cable must be grounded at the Outdoor unit whose CN41 is changed to CN40. When the
power supplying unit PAC-SC51KUA is used, connect the shielded cable to the ground
terminal on the PAC-SC51KUA.
5  MA R/C transmission cable (0.3-1.25mm
2
) must be less than 200m in length, while ME
R/C transmission cable (0.3-1.25mm
2
) must be less than 10m in length. But transmission
cable to the ME R/C can be extend using a M-NET cable (>=1.25mm
2
) when the length
is counted in the M-Net length. Both Compact MA and ME R/C transmission cables size
0.75~1.25mm
2
 in thickness.
6  MA remote controller and ME remote controller should not be grouped together.
When a PAR-31MAA is connected to a group, no other MA remote controllers can be
connected to the same group.
7  If using 1 or 2 (main/sub) MA remote controller to control more than 1 Indoor unit, use MA
transmission cable to connect all the TB15 terminals of the Indoor units. It is called
"Grouping".
If using 1 or 2 (main/sub) ME remote controller control more than 1 indoor unit, set
address to Indoor unit and ME remote controller. For the method, refer to 2-4. "Address
setting".
8  Indoor board consumes power from TB3. The power balance should be considered
according to System Design 2-3 "System configuration restrictions".
9  If Transmission booster is needed, be sure to connect the shield wires to the both sides
to the booster.
10  The critical current for choosing power source equipment is approximate
    1.4 times of total rated current of the Outdoor unit(s) or Indoor unit(s).
11  Numbers shown with ( ) indicates a diameter of the compact remote controller.
12  When System controller (SC) is connected to the system, turn the SW5-1 on.
13  The phases of electricity power must be confirmed to be right used. Phase-reverse, or     
      phase-missing could break the controllers.
* Power supply GFI, LW,
WB specifications vary
with the model of
connected indoor units
* Power supply GFI, LW,
WB specifications vary
with the model of
connected indoor units
Model
Ground-fault
interrupter
*1, *2, *4
PUHY-EP200YLM-A1
30A 100mA 0.1sec. or less
25
25
30
4
4
PUHY-EP250YLM-A1
30A 100mA 0.1sec. or less
32
32
30
4
4
PUHY-EP300YLM-A1
30A 100mA 0.1sec. or less
32
32
30
4
4
PUHY-EP350YLM-A1
40A 100mA 0.1sec. or less
40
40
40
6
6
PUHY-EP400YLM-A1
60A 100mA 0.1sec. or less
63
63
60
10
10
PUHY-EP450YLM-A1
60A 100mA 0.1sec. or less
63
63
60
10
10