3 - 80
Controller
MEE15K022
3. System remote controller
YKB/YLM 2nd
1. Specifications
(1) Device specifications
1) System configuration
2) Functions
Item
Specifications
Power supply
M-NET
17–32 VDC
Interface
M-NET transmission terminal
Connector for ALPHA2
Exclusively for connection to ALPHA2
Exclusively for connection to M-NET
Ambient
conditions
T
emperature
Operating
temperature range
-10°C – +55°C [+14°F – +131°F]
Storage
temperature range
-20°C – +60°C [-4°F – +140°F]
Humidity
30%–90% RH (Non-condensing)
Dimensions (W × H × D)
116 × 90 × 40 mm
Weight
0.4 kg [0.9lbs]
Installation conditions
Inside the metal control box
* To be used in a business office or similar environment
[4-9/16 × 3-1/2 × 1-9/16 in.]
The figure below only shows the transmission cable connections. Power cables are omitted.
AHC comprises of an ALPHA2 and an AHC ADAPTER. The use of AHC ADAPTER requires the use of ALPHA2.
The following ALPHA2 are compatible with AHC. Other types of ALPHA2 do not support AHC.
• AL2-14MR-A
• AL2-14MR-D
• AL2-24MR-A
• AL2-24MR-D
Compatible controllers [As of April 2013 (North America); June 2013 (outside North America)]
• Remote Controller: PAR-U01MEDU, PAR-U02MEDA
• Centralized Controller: EB-50GU-A, EB-50GU-J
TB7
TB3
TB7
TB3
[051]
[056]
[057]
[001]
[002]
[201]
[101]
[006]
[007]
[008]
[009]
[106]
M-NET
[003]
[004]
[005]
[103]
M-NET
M-NET
[000]
Power supply unit
PAC-SC51KUA
(optional)
Power (24 VDC)
Centralized
controller
LAN
Outdoor unit
Outdoor unit
BC controller
Group 1
Group 2
Group 3
Indoor unit
Remote controller
M-NET transmission cable
Numbers in the parentheses indicate
address numbers.
AHC
RC
RC
RC
RC
AHC
ALPHA2
AHC
ADAPTER
ALPHA2
AHC ADAPTER
AHC
* AHC ADAPTER requires either an outdoor unit or a power supply device as a power source.