3 - 73
Controller
MEE15K022
3. System remote controller
YKB/YLM 2nd
3-13. PLC software for demand input [PAC-YG41CDA]
MITSUBISHI ELECTRIC's CITY MULTI has its intelligent way to carry out peak-cut control while maximizing the air condition-
ing effect.
- Energy saving setting
- Monitoring of current energy saving
state
The registration of
energy saving control
or peak cut control is
necessary.
- Fan (thermostat OFF) control
- Stopping control
PC for TG-2000A
Collects daily
power
consumption
Collects current
daily consumption
(every per minute)
License
- Capacity saving control
(60/70/80/90%)
PLC
(Pulse counting
software installed)
PAC-YG11CDA
PLC
(PLC software
for demand input)
Requires to execute the peak cut control.
Either method should be used. These methods cannot be used together.
Counts for electric power pulse
Watt-hour
meter
or
Contact input (4 levels max.)
Demand
controller
System example
Name (Model name)
PC for central control
TG-2000A
Energy management license pack
Web monitor license
Manufacturer
PC/AT convertible unit
MITSUBISHI ELECTRIC
MITSUBISHI ELECTRIC
MITSUBISHI ELECTRIC
Remarks
Confirmed operation of DELL, HP
.
For details, refer to AE-200E/AE-50E/EW-50E/AG-150A/
EB-50GU-J T
echnical Manual.
The latest version is recommended.
AG-150A/EB-50GU-J/AE-200E/
AE-50E/EW-50E
MITSUBISHI ELECTRIC
The latest version is recommended.
Requires for each AE-200E/AE-50E/EW-50E/AG-150A/EB-50GU-J.
Requires for each AE-200E/AE-50E/EW-50E/AG-150A/EB-50GU-J.
Necessary parts for the system
- Set temperature control (
3.6
Up to 10 AE-200E/AE-50E/EW-50E/AG-150A/EB-50GU-J can be connected to 1 PLC (PLC software
for demand input). If the number of AE-200E/AE-50E/EW-50E/AG-150A/EB-50GU-J exceeds 11 sets,
more than 1 PLC is required.
AE-200E/AE-50E/
EW-50E/AG-150A/
EB-50GU-J