3 - 5
Controller
MEE15K022
2. Local remote controller
YKB/YLM 2nd
2-2. ME remote controller [PAR-U02MEDA]
1. Operation/Display
Functions
Item
Description
Setting
Display
ON/OFF
Room temp.
setting
Fan speed setting
Switches between ON and OFF.
Operation mode
switching
Switches among Cool/Dry/Fan/Auto/Heat.
*Available operation mode varies depending on the model.
The temperature can be set within the following range.
Cool/Dry: 19°C - 35°C/67°F - 95°F
Heat
: 4.5°C - 28°C/40°F - 83°F
Auto (single set point)
: 19°C - 28°C/67°F - 83°F
Auto (dual set points)
[Cool]
Same as the set temp. range for Cool mode.
[Heat]
Same as the set temp. range for Heat mode.
* Set temperature range varies depending on the model.
Changes fan speed.
* Available fan speeds vary depending on the model.
Air flow direction
setting
Changes airflow direction.
* Available airflow directions vary depending on the model.
Louver setting
Switches between louver ON/OFF.
* Available Louver setting vary depending on the model.
Ventilation
equipment
control
Interlocked setting and interlocked operation setting with the
City Multi LOSSNAY units can be made.
The Stop/Low/High settings of the ventilation equipment can
be controlled.
Backlight
Touching the screen turns the backlight on. It will stay lit for
the amount of time that was specified on the MENU screen.
Clock display
Date (year/month/day) and time (hour/minute) can be set.
The set time as well as the day of the week will be displayed
on the Home display.
The clock can be displayed in 12-hour format (AM/PM before
or after the time) and 24-hour format.
Daylight saving
Sets the daylight saving time period.
Room temp. /
humidity
display
Displays the room temperature and humidity on the Home
display.
Error information
When an error occurs, an error code and the unit address
appear.
Contact number can be set to appear when an error occurs.
(The information above needs to be entered on the Service
menu.)
Filter information
A filter sign will appear when it is time to clean the filter.
:Each group
:Not available
2. Schedule and timer setting
Item
Description
Setting
Display
Schedule
(Weekly timer)
Weekly ON/OFF times, operation mode, and set temperatures
can be set.
• Time can be set in 5-minute increments. Up to 8 schedule
patterns can be set per day of the week.
* Not valid when the ON/OFF timer is set.
:Each group
:Not available
4. Restriction settings
Item
Description
Setting
Display
Allows/disallows
local operation
Temperature
range restriction
The following operation can be prohibited by making certain
settings on the centralized controller: ON/OFF, operation mode
setting, temperature setting, fan speed, air direction, and filter sign
reset.
* While an operation is prohibited, the operation icon lights up.
Operation lock
The following operation can be prohibited respectively: ON/OFF,
operation mode setting, temperature setting, and airflow direction
setting.
The room temperature range for each operation mode can be
restricted.
Auto return
The units operate at the preset temperature after a designated
period.
(Time can be set to a value from 10 to 120 in 10-minute
increments.)
* Not valid when the temperature setting range is restricted.
Password
User password (required for schedule setting etc.) and
Service password (required for test run and function setting etc.)
can be set.
:Each group
:Not available
5. AHC control functions
Item
Description
Setting
Display
Status monitor
Displays the status of general equipments connected to the AHC.
Humidity setting
Sets the humidity level in 1% increments for the humidifier
connected to the AHC, if any.
:Each group
:Not available
6. Miscellaneous items
Item
Description
Setting
Display
Language
Selection
Select the display language from the following 8 languages.
English, French, Spanish, German, Italian, Russian, Portuguese,
and Swedish.
Service
Contains Set up and Test run.
:Each group
:Not available
3. Energy-save control assist function
Item
Description
Setting
Display
Energy-save
control during
vacancy
When vacancy is detected by the occupancy sensor, the energy-
save control assist function is activated. Four control types are
available for selection:
ON/OFF/Set temperature/Fan speed/Thermo-off.
The brightness sensor can be used in conjunction with the
occupancy sensor to detect the occupancy/vacancy status more
accurately.
The temperature range and the start/stop times can be set.
:Each group
:Not available
Timer
Night setback
ON/OFF timer
Turns ON and OFF daily at a set time.
• Time can be set in 5-minute increments.
• It is also possible to set the ON time only or the OFF time only.
Auto-OFF timer
Turns off the unit after a certain period of operation.
• Operation time can be set to a value from 30 to 240 in
10-minute increments.
ME remote
controller
ME remote
controller
(Front view)
(Side view)
(Rear view)
Unit: mm [in.]
AHC
System example
External dimension
120 [4-3/4]
83.5 [3-9/32]
140 [5-17/32]
25 [1]
46 [1-13/16]
● ME remote controller is a remote controller designed to control
Mitsubishi Electric’s air conditioning units and also allows for
the control of other manufacturer’s products connected via
Mitsubishi Electric’s AHC (Advanced HVAC CONTROLLER).
● It can control up to sixteen indoor units and one AHC.
● ME remote controller features such basic functions as operations
and monitoring of air conditioning units and schedule-control
functions and is equipped with four built-in sensors (temperature,
humidity, occupancy, brightness), which enable an integrated
control of the system, including the humidifiers and ventilation
units connected to the system via AHC, to help create a
comfortable environment.
When the built-in occupancy sensor detects vacancy in a specific
zone, the controller uses its internal function to reduce energy-
consumption.
Dual
Set