8. CAPACITY TABLES
YKB/YLM 2nd
MEE15K022
8-3. Correction by total indoor
CITY MULTI system have different capacities and inputs when many combinations of indoor units with different total capacities
are connected. Using following tables, the maximum capacity can be found to ensure the system is installed with enough capacity
for a particular application.
Total capacity of indoor units
Ratio of capacity
Ratio of power input
Total capacity of indoor units
Ratio of capacity
Ratio of power input
PURY-EP250YLM-A1
PURY-EP200YLM-A1
Cooling
Heating
50
100
200
300
150
250
350
0.2
1.2
1.0
0.8
0.6
0.4
1.0
0.8
0.6
0.4
0.2
1.2
Cooling
Heating
100
150
250
350
200
300
400
0.2
1.2
1.0
0.8
0.6
0.4
1.0
0.8
0.6
0.4
0.2
1.2
Nominal
Cooling
Capacity
Input
kW
BTU/h
kW
PURY-EP250YLM-A1
28.0
95,500
7.25
Nominal
Heating
Capacity
Input
kW
BTU/h
kW
PURY-EP250YLM-A1
31.5
107,500
8.45
Nominal
Cooling
Capacity
Input
kW
BTU/h
kW
PURY-EP200YLM-A1
22.4
76,400
5.48
Nominal
Heating
Capacity
Input
kW
BTU/h
kW
PURY-EP200YLM-A1
25.0
85,300
6.41