1 .. 522 523 524 525 526 527 528 529 530 531 532 .. 908
2 - 222
R2
MEE15K022
1. SPECIFICATIONS
YKB/YLM 2nd
 Model
PURY-P600YSLM-A1 (-BS)
 Power source
3-phase 4-wire 380-400-415 V 50/60 Hz
 Cooling capacity
*1
kW
69.0
(Nominal)
kcal/h
59,300
*1
BTU/h
235,400
Power input
kW
19.32
Current input
A
32.6-30.9-29.8
EER
kW/kW
3.57
 Temp. range of
Indoor
W.
B.
15.0~24.0°C (59~75°F)
cooling                          *3
Outdoor
D.B.
-5.0~46.0°C (23~115°F)
 Heating capacity
*2
kW
76.5
(Nominal)
kcal/h
65,800
*2
BTU/h
261,000
Power input
kW
19.12
Current input
A
32.2-30.6-29.5
COP
kW/kW
4.00
 Temp. range of
Indoor
D.B.
15.0~27.0°C (59~81°F)
 heating                          *3
Outdoor
W.
B.
-20.0~15.5°C (-4~60°F)
Indoor unit
Total capacity
50~150% of outdoor unit capacity
 connectable
Model/Quantity
P15~P250/2~50
 Sound pressure level (measured in anechoic room)
dB <A>
65.5
Sound power level (measured in anechoic room)
dB <A>
89
Refrigerant
High pressure
mm (in.
)
28.58 (1-1/8) Brazed
piping diameter
Low pressure
mm (in.
)
28.58 (1-1/8) Brazed
 Set Model
 Model
PURY-P300YLM-A1 (-BS)
PURY-P300YLM-A1 (-BS)
FAN
Type x Quantity
Propeller fan x 1
Propeller fan x 1
Air flow rate
m
3
/min
230
230
L/s
3,833
3,833
cfm
8,121
8,121
Control, Driving mechanism
Inverter-control, Direct-driven by motor
Inverter-control, Direct-driven by motor
Motor output
kW
0.92 x 1
0.92 x 1
*4
External static press.
0 Pa (0 mmH
2
O)
0 Pa (0 mmH
2
O)
Compressor
Type x Quantity
Inverter scroll hermetic compressor
Inverter scroll hermetic compressor
Manufacture
AC&R Works, MITSUBISHI ELECTRIC CORPORATION
AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method
Inverter
Inverter
Motor output
kW
8.1
8.1
Case heater
kW
- (- V)
- (- V)
Lubricant
MEL32
MEL32
 External finish
Pre-coated galvanized steel sheets (+powder coating for -BS
type)
Pre-coated galvanized steel sheets (+powder coating for -BS
type)
<MUNSELL 5Y 8/1 or similar>
<MUNSELL 5Y 8/1 or similar>
External dimension H x W x D
mm
1,710 (1,650 without legs) x 1,220 x 740
1,710 (1,650 without legs) x 1,220 x 740
in.
67-3/8 (65 without legs) x 48-1/16 x 29-3/16
67-3/8 (65 without legs) x 48-1/16 x 29-3/16
Protection devices
High pressure protection
High pressure sensor, High pressure switch at 4.15 MPa (601
psi)
High pressure sensor, High pressure switch at 4.15 MPa (601
psi)
Inverter circuit (COMP./FAN)
Over-heat protection, Over-current protection
Over-heat protection, Over-current protection
Compressor
Over-heat protection
Over-heat protection
Fan motor
Over-current protection
Over-current protection
Refrigerant
Type x original charge
R410A x 10.3 kg (23 lbs)
R410A x 10.3 kg (23 lbs)
Control
Indoor LEV and BC controller
Net weight
kg (lbs)
248 (547)
248 (547)
Heat exchanger
Salt-resistant cross fin & copper tube
Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer)
-
-
Pipe between unit and
High pressure
mm (in.)
19.05 (3/4) Brazed
19.05 (3/4) Brazed
distributor
Low pressure
mm (in.
)
22.2 (7/8) Brazed
-
 Defrosting method
Auto-defrost mode (Reversed refrigerant cycle, Hot gas)
 Drawing
External
WKJ94T181
Wiring
WKE94G041
WKE94G041
 Standard attachment
Document
Installation Manual
Accessory
Refrigerant conn. pipe
 Optional parts
Outdoor Twinning kit: CMY-R100VBK2
Joint: CMY-Y102SS-G2,CMY-Y102LS-G2,CMY-R160-J1
Main BC controller: CMB-P108,1010,1013,1016V-GA1
Sub BC controller: CMB-P104,108V-GB1,CMB-P1016V-HB1
Remarks
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.
Notes:
Unit converter
1.Nominal cooling conditions (subject to JIS B8615-2)
   Indoor: 27°CD.B.
/19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B.
/24°CW.B. (95°FD.
B./75°FW.B.
)
   Pipe length: 7.5 m (24-9/16 ft.
), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-2)
   Indoor: 20°CD.B.
 (68°FD.B.), Outdoor: 7°CD.B./6°CW.
B. (45°FD.B.
/43°FW.B.)
   Pipe length: 7.5 m (24-9/16 ft.
), Level difference: 0 m (0 ft.)
 3.-5°CD.B. (23°FD.
B.)/-6°CW.B.
 (21°FW.B.
) to 21°CD.B. (70°FD.
B.)/15.5°CW.B. (60°FW.B.)
   with cooling/heating mixed operation.
4.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH
2
O, 6.1 mmH
2
O).
BTU/h
=kW x 3,412
cfm
=m
3
/min x 35.31
lbs
=kg/0.4536
 *Above specification data is