1 .. 505 506 507 508 509 510 511 512 513 514 515 .. 908
2 - 205
8. CAPACITY TABLES
YKB/YLM 2nd
Y (HIGH COP)
MEE15K022
8-4-2. Heating capacity correction
8-4-3. How to obtain the equivalent piping length
0.90
0
20
40
60
80
100
120
140
160
180
Heating capacity correction factor
0.95
1.00
Piping equivalent length (m)
PUHY-EP200, 250YLM-A1(-BS)
0.90
0
20
40
60
80
100
120
140
160
180
Heating capacity correction factor
0.95
1.00
Piping equivalent length (m)
PUHY-EP700, 750, 800YSLM-A1(-BS)
0.90
0
20
40
60
80
100
120
140
160
180
Heating capacity correction factor
0.95
1.00
Piping equivalent length (m)
PUHY-EP300, 350, 400, 450YLM-A1(-BS)
0.90
0
20
40
60
80
100
120
140
160
180
Heating capacity correction factor
0.95
1.00
Piping equivalent length (m)
PUHY-EP850, 900, 950, 1000YSLM-A1(-BS)
0.90
0
20
40
60
80
100
120
140
160
180
Heating capacity correction factor
0.95
1.00
Piping equivalent length (m)
PUHY-EP500, 550, 600, 650Y(S)LM-A1(-BS)
0.85
0.90
0
20
40
60
80
100
120
140
160
180
Heating capacity correction factor
0.95
1.00
Piping equivalent length (m)
PUHY-EP1050,1100,1150,1200,1250,1300,1350YSLM-A1(-BS)
1   PUHY
-EP200YLM-A1(-BS)
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.42 × number of bends in the piping) m
2   PUHY
-EP250YLM-A1(-BS)
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.42 × number of bends in the piping) m
3   PUHY
-EP300YLM-A1(-BS)
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.47 × number of bends in the piping) m
4   PUHY
-EP350YLM-A1(-BS)
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.47 × number of bends in the piping) m
5   PUHY
-EP400, 450, 500, 550, 600, 650Y(S)LM-A1(-BS)
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.50 × number of bends in the piping) m
6   PUHY
-EP700, 750, 800YSLM-A1(-BS)
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.70 × number of bends in the piping) m
7   PUHY
-EP850, 900, 950, 1000, 1050, 1100, 1150, 1200, 1250, 1300, 1350YSLM-A1(-BS)
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.80 × number of bends in the piping) m