1 .. 461 462 463 464 465 466 467 468 469 470 471 .. 908
2 - 161
6. VIBRATION LEVEL
YKB/YLM 2nd
Y (HIGH COP)
MEE15K022
6. VIBRATION LEVEL
[PUHY-EP200-500YLM, PUHY-EP550-1350YSLM]
* Vibration level varies depending on the conditions of actual installation site.
20cm
10cm
Concrete
Service panel side
Measurement point
Measurement condition
Measurement frequency: 1 Hz-80 Hz
Measurement point: Ground surface 20 cm away from the unit leg
Installation condition: Direct installation on the concrete floor
Power source: 3-phase 4-wire 380-400-415 V 50/60 Hz
Operation condition: JIS condition (cooling, heating)
Measurement device: Vibration level meter for vibration pollution VM-1220C (JIS-compliant product)
Vibration level
Model
Vibration level (dB)
PUHY-EP200YLM-A1 (-BS)
46
PUHY-EP250YLM-A1 (-BS)
46
PUHY-EP300YLM-A1 (-BS)
47
PUHY-EP350YLM-A1 (-BS)
47
PUHY-EP400YLM-A1 (-BS)
47
PUHY-EP450YLM-A1 (-BS)
47
PUHY-EP500YLM-A1 (-BS)
48
PUHY-EP550YSLM-A1 (-BS)
49.5
PUHY-EP600YSLM-A1 (-BS)
50
PUHY-EP650YSLM-A1 (-BS)
51
PUHY-EP700YSLM-A1 (-BS)
51
PUHY-EP750YSLM-A1 (-BS)
51.5
PUHY-EP800YSLM-A1 (-BS)
51.5
PUHY-EP850YSLM-A1 (-BS)
51.5
PUHY-EP900YSLM-A1 (-BS)
52
PUHY-EP950YSLM-A1 (-BS)
52
PUHY-EP1000YSLM-A1 (-BS)
52
PUHY-EP1050YSLM-A1 (-BS)
52
PUHY-EP1100YSLM-A1 (-BS)
52
PUHY-EP1150YSLM-A1 (-BS)
52
PUHY-EP1200YSLM-A1 (-BS)
52
PUHY-EP1250YSLM-A1 (-BS)
52
PUHY-EP1300YSLM-A1 (-BS)
52
PUHY-EP1350YSLM-A1 (-BS)
52